W415-0788 / F / 10.21.13

6

EN

4.1B

The installation must conform with local codes or, in

absence of local codes, the National Gas and Propane

Installation Code CSA B149.1 in Canada, or the National

Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United

States. Suitable for mobile home installation if installed in

accordance with the current standard CAN/CSA Z240MH

Series, for gas equipped mobile homes, in Canada or

ANSI Z223.1 and NFPA 54 in the United States.

As long as the required clearance to combustibles is

maintained, the most desirable and benefi cial location

for an appliance is in the center of a building, thereby

allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the

room where the appliance is to be located should be considered. If possible, you should choose a location

where the vent will pass through the house without cutting a fl oor or roof joist.

If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood

fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.

Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must

be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.

We suggest that our gas
hearth products be installed
and serviced by professionals
who are certified in the U.S.
by the National Fireplace
Institute

® (NFI) as NFI Gas

Specialists

www.nficertified.org

When the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.

The appliance, when installed with a blower, must be electrically connected and grounded in accordance with
local codes. In the absence of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada
or the ANSI/NFPA 70-1996 National Electrical Code in the United States. The blower power cord must be
connected into a properly grounded receptacle. The grounding prong must not be removed from the cord plug.

2.3 GENERAL

INFORMATION

FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION

AND QUALITY!

GDS60

GS60

NG

LP

NG

LP

Altitude (FT)

0-4,500

0-4500

0-4500

0-4500

Max. Input (BTU/HR)

35,000 (Top vent)

21, 000 (Rear vent only)

31,500 (Top vent)

21,000 (Rear vent only)

35, 000

31,500

Max. Output (BTU/
HR)

27,300

24,570

27,300

24,570

Max. Steady State
Effi ciency (w/the fan
on)

78%

78%

78%

78%

Max. A.F.U.E.

72%

71%

72%

71%

Min. Inlet Gas Supply
Pressure

4.5" (11mb)

Water Column

11" (27mb)

Water Column

4.5" (11mb)

Water Column

11" (27mb)

Water Column

Max. Inlet Gas Sup-
ply Pressure

7" (17mb)

Water Column

13" (33mb)

Water Column

7" (17mb)

Water Column

13" (33mb)

Water Column

Manifold Pressure
(Under Flow
Conditions)

3.5" (9mb)

Water Column

10" (25mb)

Water Column

3.5" (9mb)

Water Column

10" (25mb)

Water Column