3.5 DEFINITIONS

14.2

For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
H

T

- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet

H

R

- combined horizontal vent lengths in feet

H

O

- offset factor: .03 (total degrees of offset - 135°*) in feet

V

T

- combined vertical vent lengths in feet

3.6 ELBOW VENT LENGTH VALUES

15.2A

FEET

INCHES

MILLIMETERS

1° 0.03

0.5 12.7

15° 0.45

6.0

152.4

30° 0.9

11.0

279.4

45°* 1.35

16.0

406.4

90°*

2.7

32.0

812.8

* The fi rst 45° and 90°offset has a zero value and is shown in the formula as -45° and - 90° respectively or
-135° when combined.