ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RAN OUT,
WITH THE GLASS DOOR OPEN OR REMOVED.
TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THE APPLIANCE.
APPLIANCE MAY BE HOT, DO NOT SERVICE UNTIL APPLIANCE HAS COOLED.
DO NOT USE ABRASIVE CLEANERS.
SYMPTOM
PROBLEM
TEST SOLUTION
Main burner
fl ame is a
blue, lazy,
transparent
fl ame.
Blockage in vent.
-
Remove blockage. In really cold conditions, ice buildup
may occur on the terminal and should be removed as
required. To minimize this from happening again, it is
recommended that the vent lengths that pass through
unheated spaces (attics, garages, crawl spaces) be
wrapped with an insulated mylar sleeve. Prevent sleeve
from sagging. Contact your local authorized dealer for
more information.
Incorrect installation.
-
Refer to “VENTING” section to ensure correct location of
storm collars.
Flames are
consistently
too large or
too small.
Carboning
occurs.
Unit is over-fi red or
underfi red.
-
Check pressure readings:
Inlet pressure
can be checked by turning screw (A)
counter-clockwise 2 or 3 turns and then placing pressure
gauge tubing over the test point. Gauge should read
7” (minimum 4.5”) water column for natural gas or 13”
(minimum 11”) water column for propane. Check that
main burner is operating on ‘HI’.
Outlet pressure
can be checked the same as above
using screw (B). Gauge should read 3.5” water column
for natural gas or 10” water column for propane. Check
that main burner is operating on ‘HI’.
AFTER TAKING PRESSURE READINGS, BE SURE
TO TURN SCREWS CLOCKWISE FIRMLY TO
RESEAL. DO NOT OVER TORQUE.
Leak test with a soap and water solution.
Carbon
is being
deposited on
glass, burner
media or
combustion
chamber
surfaces.
Air shutter has become
blocked.
-
Ensure air shutter opening is free of lint or other
obstructions.
Flame is impinging on
the burner media or
combustion chamber.
-
Check that the burner media is correctly positioned.
-
Open air shutter to increase the primary air.
-
Check the input rate: check the manifold pressure and
orifi ce size as specifi ed by the rating plate values.
-
Check that the door gasketing is not broken or missing
and that the seal is tight.
-
Check that both vent liners are free of holes and well
sealed at all joints.
-
Check that minimum rise per foot has been adhered to
for any horizontal venting.
White / grey
fi lm forms.
Sulphur from fuel is
being deposited on
glass, burner media or
combustion chamber
surfaces.
-
Clean the glass with a recommended gas fi replace glass
cleaner. DO NOT CLEAN GLASS WHEN HOT.
-
If deposits are not cleaned off regularly, the glass may
become permanently marked.
Exhaust
fumes smelled
in room,
headaches.
Fireplace is spilling.
-
Ensure exhaust bracket gasket seal.
-
Check door seal.
-
Check for exhaust blockage.
-
Check that venting is installed correctly.
-
Room is in negative pressure; increase fresh air supply.
42.2B