seCtIOn 7 |

Preparing the Charger for Operation

- Stage 1 and Stage 3. This also applies when two banks of batteries are being charged
simultaneously and the batteries in the two banks are in a dissimilar state of discharge.
A pair of switches S1 & S2 out of a set of 4 DIP Switches has been provided for selecting
the battery type and for modifying the Stage 2 Absorption Stage when charging loaded
batteries / two banks of batteries with different discharged states. The following selec-
tions can be made with the help of the DIP Switches S1 and S2:

!

cAUtion!

Do not change the DIP Switch setting when the charger is operating. Always
change the DIP Switch setting when the charger is OFF, i.e. after disconnecting
the charger from the AC input power).
note: The voltages are for battery temperature of 77ºF / 25ºC.

diP SWitcH SettinG FoR Sec-1250Ul

S1

S2

Float

Absorption

Battery

type

charging

Stages

off*

ON*

13.5V*

14.4V*

Flooded /

AGM*

3 Stages

(Stages 1, 2, 3)

ON

off

13.5V

14.0V

Gel Cell

3 Stages

(Stages 1, 2, 3)

off

off

13.5V

Disabled

battery with

Load

2 Stages

(Stages 1, 3)

ON

ON

caution! do not use this setting

* factory pre-set in this position

diP SWitcH SettinGS - Sec-2425Ul

S1

S2

Float

Absorption

Battery type

charging

Stages

off*

ON*

27V*

28.8V*

Flooded /

AGM*

3 Stages

(Stages 1, 2, 3)

ON

off

27V

28.0V

Gel Cell

3 Stages

(Stages 1, 2, 3)

off

off

27V

Disabled

battery with

load

2 Stages

(Stages 1, 3)

ON

ON

caution! do not use this setting

* factory pre-set in this position