STEINEL HFLUM2-120 Manuel d'utilisation

Page 2

Advertising
background image

Product Overview

120VAC

60Hz

HF

5.8 GHz

360°

Usage considerations

• When fl uorescent lamps are new or

at cold temperatures, the sensor may

detect gas moving inside the lamps.

In this case, switch the lights OFF and

reduce the reach setting.

• Use only high quality brand-name

lamps.

• Fixture confi gurations can vary

considerably. Since metal surfaces

refl ect high-frequency signals, the

detection pattern may vary from the

standard published coverages or

reach. Each fi xture design must be

tested for proper coverage accuracy.

• Consider the interaction between

various OEM components such as

ballast and lamp types. All components

should be tested for complete

compatibility as a system.

• The HFLUM2-120 is a UL/CUL

Listed open type device that requires

installation in a fi xture or listed junction

box or enclosure.

• One HFLUM2-120

• Installation Instructions

Needed for installation

• Two mounting screws

• Fixture or listed enclosure

Applications

• Wide variety of interior spaces

including offi ces, conference rooms,

classrooms

Intended uses

• For indoor use only

• Sensor mounts inside a lighting fi xture

Package Contents

Installation Overview

www.steinel.net (800) 852-4343

WARNING

• Turn power off at the circuit breaker before installing the sensor

• Sensor module must be installed and used in accordance with appropriate

electrical codes and regulations

• Installation by a qualifi ed electrician is recommended

Voltage

Load

rating

Transmitter power

Power consumption

Time delay

Light level

HF System

Coverage

Dimensions

5 year warranty

UL and CUL Listed, RoHS Compliant

120 VAC, 60 Hz

0-600 watt incandescent, 0-150 watt magnetic or electronic ballast,
2 ballast, max 50uF

1mW

< 0.5W

30 sec to 30 min

.2 - 200 footcandles ; 2 - 2000 lux

5.8 GHz

360°, 3.3 to 26 foot reach

4.2 x 1.7 x 1.8 in; 107 x 42 x 44.5 mm

Product description

Specifi cations

The HFLUM2-120 is a line voltage

occupancy sensor module that installs in

a fi xture, adding energy saving lighting

control in each fi xture location. The

sensor uses STEINEL’s High Frequency

(HF) technology to turn lighting on and off

based on occupancy. Also, it holds lights

off when suffi cient daylight is present.

www.steinel.net (800) 852-4343

2

3

Fixture

integrated

Mounting tabs (2)

Light level, sensitivity, and time adjustments

Photocell

Sensor dome antenna

Wire terminations

1

2

3

4

5

2

1

3

4

5

The HFLUM2-120 emits high frequency

electromagnetic waves (5.8 GHz).

Movement in the controlled area causes a

change in the echo, resulting in detection.

HF sensors detect motion through many

materials, including panes of glass or

through the lens of a fi xture, enabling the

sensor to be hidden from view.

INST_HFLUM_newLayout_ENU-FRA.indd 4-5

INST_HFLUM_newLayout_ENU-FRA.indd 4-5

12.04.11 16:53

12.04.11 16:53

Advertising