Setup & Commissioning

Test mode

• Ensure that the sensor is in test mode.

- set time delay to minimum setting of

15 seconds

- set light level to maximum (“day” setting,

light level function overridden - factory

setting)

• Turn power ON at the circuit breaker (lights

will turn ON). After a warm up period of up

to one minute, lights will turn OFF if the

sensor does not detect motion.

• Walk in view of sensor, lights should turn

ON. Be still for 15 seconds and lights

should turn OFF.

Light level

The light level feature allows lighting to remain

OFF during daylight, regardless of occupancy.

Daytime operation is at 200 footcandles

(factory setting). Nighttime operation is at

.2 footcandles.

Light level teach mode

The light level teach mode reads the ambient

light level in the space and selects this amount

for the light level setting.

• Turn the light level setting to

• After 10 seconds, the value of the ambient

brightness is saved.

• This value is also available after a power

failure if the potentiometer is set to teach

mode at power up.

Time delay

Time delay is the period of time lights remain

on after the last detection. Adjustment ranges

from 15 seconds to 30 minutes. Factory

setting is 15 minutes.

After setup and commissioning tests are

complete, adjust the time delay and light level

settings to fi t the application needs.

Setup & Commissioning

Time

ON

1 2 3

4

Time Delay DIP Switch

1

ON

ON

OFF

ON

ON

OFF

OFF

OFF

N/A

2

ON

OFF

ON

OFF

ON

ON

OFF

OFF

N/A

3

ON

OFF

ON

ON

OFF

OFF

ON

OFF

N/A

4

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

Time

15 sec

1 min

5 min

10 min

15 min

20 min

25 min

30 min

override

Light level: .2 (night) to 200 (day) footcandles

Low

High

HBS 300 Coverage

The HBS 300 contains three pyroelectric

sensors to detect occupancy. At an installation

height of 8 to 45 feet, maximum reach is 22

feet radial and 60 feet tangential. If needed,

the detection zone can be adjusted (see

below).

Coverage may vary depending on mounting

height and environmental conditions.

HBS 200 Coverage

The HBS 200 contains two pyroelectric

sensors to detect occupancy and has an aisle

way coverage of up to 100 feet when mounted

at 40 ft. If needed, the detection zone can be

adjusted with a lens cover (see below).

In addition, the view of the HBS 200 can be

rotated 90 degrees. To do this, remove the

sensor housing from the back box by pressing

the tabs on either side of the sensor.

Coverage may vary depending on mounting

height and environmental conditions.

10
20
30
40

40 ft

50

50

40

40

35 ft

22 ft 22 ft

35 ft

10
20
30
40

radial

tangential

40 ft

13 ft

50 ft

53 ft 53 ft

50 ft

8

9