Wiring

Before installation, make sure that power has

been switched off at the breaker and check that

the circuit is dead with a voltage tester.

The leads consist of three wires:

Black = line

White = neutral

Red = load

If in doubt, identify the individual conductors with

a voltage tester or contact a qualifi ed electrician.

Operation

L
O
A
D

LINE (BLACK)

NEUTRAL (WHITE)

NEUTRAL

HOT

LOAD (RED)

The HBS 300 and HBS 200 operate by turning

lights ON automatically when occupancy

is detected and OFF when the space is left

vacant and the time delay has elapsed.

Light level function

The light level feature keeps lighting

OFF during daylight hours, regardless of

occupancy. A light level delay-off function

prevents the sensor from responding to

temporary changes in ambient light level. If

the ambient light level is brighter than the set

target value, the sensor will wait for one minute

before turning lights OFF. If motion is detected

within this time, lights will remain ON. After no

motion is detected for one minute and the light

level has been greater than the target value,

the lights will turn OFF and remain OFF until

the daylight level drops below the target set

point and motion is detected.

Initial power up

Upon initial power up, the load will turn ON

for up to one minute. If no motion is detected,

the load will switch OFF. If motion is detected

and the target light level setting is less than

the daylight level, the load will stay ON for the

selected time delay setting (per DIP switch

setting). If the daylight level at power up is

greater than the target light level setting, the

load will switch OFF regardless of occupancy.

Surge protection

The surge protection feature will reset the

sensor automatically after: power surges,

power outages, and power shortages. Surge

protection protects the sensor if it is miswired

as well. If miswired, shut off power, correct

the wiring, and the sensor will then operate

correctly.

Wireless Group Control

Any HBS 300 or HBS 200 sensor can have the

option of wireless group control by adding an

MF1-UL Wireless Group Control Module.

Standard wiring for the HBS 300 and HBS 200 High Bay Occupancy Sensors

HBS sensor
back box

MF1-UL
Wireless Group
Controller

HBS sensor
housing

6

7

www.steinel.net (800) 852-4343

www.steinel.net (800) 852-4343