Setup & Commissioning

Test mode

• Ensure that the sensor is in test mode.

- set time delay to minimum setting of

10 seconds

- set light level to maximum

(“day” setting, light level function

overridden)

• Turn power ON at the circuit breaker

(lights will turn ON). After a warm up

period of up to one minute, lights will

turn OFF if the sensor does not detect

motion.

• Walk in view of sensor, lights should

turn ON. Be still for 10 seconds and

lights should turn OFF.

Light level

The light level feature allows lighting to

remain OFF during daylight, regardless of

occupancy. Daytime operation is at 200

footcandles (factory setting). Nighttime

operation is at .2 footcandles.

Time delay

Time delay is the period of time lights

remain on after the last detection.

Adjustment ranges from 10 sec (factory

setting) to 15 min.

After setup and commissioning tests are

complete, adjust the time delay and light

level settings to fi t the application needs.

7

Wiring

Operation

When installing, make sure power has

been switched off at the breaker and

check that the circuit is dead with a

voltage tester.

The leads consist of two wires:

L = hot wire (black)

N = neutral wire (white)

If in doubt, identify the individual

conductors with a voltage tester or

contact a qualifi ed electrician.

The FL 300 operates by turning lights

on automatically when occupancy is

detected and off when the space is left

vacant.

Light level function

The light level feature keeps lighting

off during daylight hours, regardless of

occupancy.

Manual override

Adding a wall switch provides a manual

override function. While the switch is ON,

the sensor is in occupancy control mode.

Users can turn the switch OFF at any time

to keep lights OFF.

The switch can be used to override lights

ON for 4 hours. To do this, the switch

must be in the ON position and the sensor

has gone through warm up. Toggle switch

OFF ON OFF ON within 2 seconds. Lights

will now remain on for 4 hours. To verify

that the sensor is in manual override, you

should see a red indicator light behind the

lens in the upper right hand corner.

To resume sensor mode prior to the 4

hours, simply fl ip the switch OFF ON

once within two seconds. Lights will

turn off and the sensor returns to sensor

mode.

Surge protection

Every sensor contains built in surge

protection. This feature will reset the

unit automatically after: power surges,

power outages, and power shortages.

Surge protection protects the sensor if it

is miswired as well. If miswired, shut off

power, correct the wiring, and the sensor

will then operate correctly.

Time delay: 10 seconds to 15 minutes

Light level: .2 (night) to 200 (day) footcandles

6