Minimum/Maximum
Supply Pressure
“W.C. for
propane
8/12
Minimum/Maximum
Supply Pressure
“W.C. for
Natural Gas
8/12
Head Setting
4
Air Setting (Riello Air
Gate)
3.5
APPROVAL AGENCY
OMNI-Test
Laboratories
DRY WEIGHT (lbs)
480
Dimensions
70" X 26" X 53"
FLUE SIZE
6”
Certification File #
367-S-03b-5
CONNECTING THE CYLINDER
IF CYLINDERS ARE USED TO SUPPLY THE HEATER, NO CYLINDERS SMALLER THAN 100
LB CAPACITY SHALL BE USED. THESE CYLINDERS MUST SUPPLY A VAPOUR
WITHDRAWAL ONLY.
1.) ALL CYLINDER CONNECTIONS MUST BE MADE USING A WRENCH TO TIGHTEN THE
POL FITTING.
2.) BE SURE THAT THE CYLINDER VALVE IS IN THE CLOSED POSITION WHEN
CONNECTING OR DISCONNECTING THE CYLINDER.
3.) PROPER PROCEDURE FOR GAS LEAK TESTING: A SOAP AND WATER SOLUTION
MUST BE APPLIED TO ALL CONNECTIONS IN ORDER TO LEAK CHECK THE SYSTEM.
4.) THE HOSE ASSEMBLY MUST BE VISUALLY INSPECTED PRIOR TO EACH USE OF
THE HEATER.
THE GAS MUST BE TURNED OFF AT THE PROPANE SUPPLY CYLINDER(S) WHEN THE
HEATER IS NOT IN USE. WHEN THE HEATER IS TO BE STORED INDOORS, THE
CONNECTION BETWEEN THE PROPANE SUPPLY CYLINDER(S) AND THE HEAtER MUST BE
DISCONNECTED AND THE CYLINDERS REMOVED FROM THE HEATER AND STORED IN
ACCORDANCE WITH STANDARDS FOR THE STORAGE AND HANDLING OF LIQUEFIED