Troubleshooting, Troubleshooting procedures for verona wall – Zephyr ZVO-M90AG Manuel d'utilisation

Page 16

Advertising
background image

14

www.zephyronline.com

T

roubleshooting

TROUBLESHOOTING PROCEDURES FOR VERONA WALL

Issue

Cause

What to do

After installation,
the unit doesn’t
work.

1. The power source is not turned ON.

1. Make sure the circuit breaker and the unit’s

power is ON.

2. The power line and the cable locking connector

is not connecting properly.

2. Check the power connection with the unit is

connected properly.

3. The wires on the control board are loose.

3. Make sure the wires on the control board are

connected properly.

4. The switch board and control board wirings are

disconnected.

4. Make sure the wirings between the switch

board and control board are connected
properly.

5. The switch board or control board is defective.

5. Change the switch board or control board.

Light works, but
blower is not
turning.

1. The blower cable is disconnected.

1. Check all wirings from the blower to be sure

all cables are connected properly.

2. The blower is defective, possibly seized.

2. Change the blower.

3. The thermally protected system detects if the

blower is too hot to operate and shuts the blower
down.

3. The blower will function properly after the

thermally protected system cool down.

4. The switch board or control board is defective.

4. Change defective part.

The unit is
vibrating.

1. The motor is not secure in place.

1. Tighten the motor in place.

2. Damaged blower wheel.

2. Replace the blower.

3. The hood is not secured in place.

3. Check the installation of the hood.

The unit is
whistling.

1. The fi lter is not in the correct position.

1. Adjust the fi lters until the whistling stops.

2. The duct pipe connections are not sealed or

connected properly.

2. Check the duct pipe connections to be sure all

connections are sealed properly.

The blower is
working, but the
lights are not.

1. Defective LED bulb.

1. Change the LED bulb.

2. The LED bulb wire is loose.

2. Check LED wire connections at the control

board and the LED light bulbs. Reconnect any
loose wires.

The speed levels
of the blower
sound the same.

1. Using the wrong size of ducting.

1. Change the ducting to at least 8” or higher.

2. ACT enabled blower CFM set to 290 or 440

CFM.

2. Noise level distinction between some speeds

may be minimal when ACT enabled blower is
set to 290 or 440 CFM.

The hood is
not venting out
properly.

1. The hood might be hanging too high from the

cook top.

1. Adjust the distance between the cook top and

the bottom of the hood within 26” and 34”
range.

2. The wind from the opened windows or opened

doors in the surrounding area are affecting the
ventilation of the hood.

2. Close all the windows and doors to eliminate

the outside wind fl ow.

3. Blockage in the duct opening or ductwork.

3. Remove all the blocking from the duct work or

duct opening.

4. The direction of duct opening is against the wind.

4. Adjust the duct opening direction.

5. Using the wrong size of ducting.

5. Change the ducting to at least 8” or higher for

the internal blower.

Mesh Filter is
vibrating.

1. Mesh fi lter is loose.

1. Make sure the metal clips in the handle are

not stuck. Or replace the mesh fi lter.

2. Filter spring clip is loose or broken.

2. Uninstall and reinstall fi lter, push up on fi lter

latch. Replace mesh fi lter if needed.