Sensor Testing

If the sensor is disconnected or short-circuited, the heating system is
turned off. Test your sensor according to the following resistance table:

Error Codes

E0: Internal error. The thermostat must be replaced.
E2: External sensor short-circuited or disconnected.

Sensor

Temp (˚C)

Temp (˚F)

Value (ohm)

–10

–14

64000

0

32

38000

10

50

23300

20

68

14800

30

86

9700