See also CLEARANCE REQUIREMENTS on the next page.

Exhaust direction

Directional exhausting can be accomplished by installing

a quick-turn 90° dryer vent elbow directly to exhaust

outlet of dryer. Dryer vent elbows are available through

your local parts distributor or hardware store.

Exhaust system requirements, continued

INSTALLATION REQUIREMENTS

In installations where the exhaust system is not described

in the charts, the following method must be used to

determine if the exhaust system is acceptable:
1 Connect an inclined or digital manometer between

the dryer and the point the exhaust connects to the

dryer.

2 Set the dryer timer and temperature to air fl uff

(cool down) and start the dryer.

3 Read the measurement on the manometer.
4 The system back pressure MUST NOT be higher

than 0.75 inches of water column. If the

system back pressure is less than 0.75 inches of

water column, the system is acceptable. If the

manometer reading is higher than .075 inches of

water column, the system is too restrictive and the

installation is unacceptable.

Although vertical orientation of the exhaust system is

acceptable, certain extenuating circumstances could

affect the performance of the dryer:

Only the rigid metal duct work should be used.

Venting vertically through a roof may expose the

exhaust system to down drafts causing an increase

in vent restriction.
Running the exhaust system through an

uninsulated area may cause condensation and

faster accumulation of lint.
Compression or crimping of the exhaust system will

cause an increase in vent restriction.
The exhaust system should be inspected and

cleaned a minimum of every 18 months with

normal usage. The more the dryer is used, the

more often you should check the exhaust system

and vent hood for proper operation.

Í

NOTE

Use of 90° quick-turn elbow required to meet minimum

installation depth of free-standing dryer:

Straight back venting allows for 0” (0 cm) installation.

Venting right with 90° elbow allows for 0.75” (2 cm)

installation.

Venting downward with 90° elbow allows for 0.75” (2

cm) installation.

Venting left with short, straight adapter and 90°

elbow allows for 3.75” (9.5 cm) installation.

Venting upward with short, straight adapter and 90°

elbow allows for 4” (10.5 cm) installation.

Install male fi ttings in correct direction:

CORRECT

INCORRECT