Installing the Insert

(continued)

Figure 3. Minimum height from roof to lowest
discharge opening

ROOF PITCH

H (MIN.) FT.

Flat to 6/12

1.0

6/12 to 7/12

1.25

Over 7/12 to 8/12

1.5

Over 8/12 to 9/12

2.0

Over 9/12 to 10/12

2.5

Over 10/12 to 11/12

3.25

Over 11/12 to 12/12

4.0

Over 12/12 to 14/12

5.0

Over 14/12 to 16/12

6.0

Over 16/12 to 18/12

7.0

Over 18/12 to 20/12

7.5

Over 20/12 to 21/12

8.0

!

WARNING: MAJOR U.S. BUILDING CODES
SPECIFY MINIMUM CHIMNEY AND/OR VENT
HEIGHT ABOVE THE ROOF TOP. THESE
MINIMUM HEIGHTS ARE NECESSARY IN THE
INTEREST OF SAFETY. SEE THE FOLLOWING
DIAGRAM FOR MINIMUM HEIGHTS, PROVIDED
THE TERMINATION CAP IS AT LEAST 2-FEET
FROM A VERTICAL WALL AND 2 FEET BELOW
A HORIZONTAL OVERHANG.

Note: This also pertains to vertical vent systems installed
on the outside of the building.

PENTE DU TOIT

H (MINI.) EN CM

De plat à 6/12

30

De 6/12 à 7/12

38

De 7/12 à 8/12

46

De 8/12 à 9/12

61

De 9/12 à 10/12

76

De 10/12 à 11/12

99

De 11/12 à 12/12

122

De 12/12 à 14/12

152

De 14/12 à 16/12

183

De 16/12 à 18/12

213

De 18/12 à 20/12

229

De 20/12 à 21/12

244

Installation de la cassette

(suite)

!

AVERTISSEMENT : LES PRINCIPAUX CODES DE
CONSTRUCTION AMÉRICAINS DÉFINISSENT LA
HAUTEUR MINIMALE DE LA CHEMINÉE ET/OU
DU CONDUIT D’ÉVACUATION AU-DESSUS DU
TOIT. CES HAUTEURS MINIMALES SONT
NÉCESSAIRES POUR DES RAISONS DE
SÉCURITÉ. CONSULTEZ LE SCHÉMA SUIVANT
POUR CONNAÎTRE LES HAUTEURS MINIMALES
À RESPECTER LORSQUE LE CAPUCHON EST
ÉLOIGNÉ D’AU MOINS 61 CM D’UN MUR
VERTICAL ET AU-DESSOUS D’UN SURPLOMB.

Remarque : Ces restrictions s’appliquent également aux
systèmes d’évacuation verticale installés à l’extérieur de
l’édifice.

Figure 3. Hauteur minimum entre le toit et
l’ouverture d’évacuation la plus
basse

HORIZONTAL OVERHANG

(SURPLOMB)

VERTICAL WALL

(MUR VERTICAL)

TERMINATION CAP

(CAPUCHON)

12

X

ROOF PITCH IS X/ 12
(LA PENTE DU TOIT EST DE X/12)

LOWEST

DISCHARGE

OPENING

(L’OUVERTURE

D’ÉVACUATION LA

PLUS BASSE)

H (MINI.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
(H (MINI) - HAUTEUR MINIMUM ENTRE LE TOIT
ET L’OUVERTURE D’ÉVACUATION LA PLUS BASSE)

2 FT

(61cm)

MINI.

2 FT (61cm)

MINI.

Advertising