Operating Instructions and Owner’s Manual

enerco Group, Inc. | Gas-Fired Infra-Red Space Heaters

cOnnectiOn diagraM FOr FlaMe rOd current
FOr FlaMe rectiFicatiOn sYsteMs (dsp-5, a5)

Means OF prOVing adeQuate grOunding area

The proper flame-rod-to-ground-area ratio cannot
always be determined by visual examination or physical
measurement. A positive means of checking the instal-
lation is the measurement of the flame rod current
under actual firing conditions. It is definitely recom-
mended that the installer measure the current flow be-
tween the lead of the flame rod unit and the terminal
in the control terminal board (see Figure 3). Measure
the current with a DC Microammeter or equal. We
recommend a steady output of .9 microamperes or
more. A steady flow of current in this amount under
actual firing conditions will generally indicate adequate
grounding of the pilot flame.

nOte:
1. Read all control data sheet supplied with this heater.
2. Check flame rod for any contact to heater parts. Flame

rod must be free of any contact to heater. Contact with
heater will short circuit flame rod.

3. Cracked porcelain on flame rod will short circuit sensor.

Replace flame rod.

Figure 3 – Using a microammeter to prove adequate grounding area.

Gas

Flame

Flame

Rod

Flame
Rod Assy.

Microammeter

Control

Terminal For
Flame Rod
loadwire

g

tHerMOstat

Thermostat

Powerpile Thermocouple
Honeywell Q313A

Factory wired

Powerpile Gas Valve – Honeywell VS820

WIRe
SIZeS

MAXIMUM

leNGTH

oF WIRe

CABle

No 18

15 FeeT

No 16

30 FeeT

No 14

50 FeeT

CAUTION TO INSTALLER

NEVER CONNECT POWERPILE
GAS VALVE OR THERMOSTAT
TO LINE VOLTAGE OR A
TRANSFORMER.

NOTE

Do not exceed the

maximum lengths listed in the
table when wiring between the
Thermostat and Gas Valve with
cable not supplied by HeAT STAR.

CONNECTION DIAGRAM