3

INSTALLATION RESTRICTIONS

Failure to install, maintain and/or operate the Rooftop Inducer in accordance with manufacturer's instructions may result in conditions
which can produce bodily injury and property damage.

The Rooftop Inducer must be installed by a qualified installer in accordance with these instructions and all local codes or in their
absence in accordance with the latest edition of The National Fuel Gas Code (NFPA 54), NFPA 211 or 31 when applicable, the latest
edition of the National Electrical Code (NFPA 70) and the Occupational Safety and Health Act (OSHA) when applicable. In the
absence of local codes in Canada, installations must comply with the Canadian Electrical Code (CSA Std 22.1 ), the latest edition of
the Natural Gas Installation Code (CAN/CGA-B149.1), the Propane Installation Code (CAN/CGA-B149.2) and the Installation Code for
Oil Burning Equipment (CSA Std B139-M91).

Improper installation can create a hazardous condition such as an explosion, fire, electrical shock or carbon monoxide poisoning
resulting in property damage, personal injury or death.

1. The Rooftop Inducer may be installed on natural gas, LP-gas, oil-fired, solid fuel heating systems or general ventilation systems.

The Rooftop Inducer is not suitable for use on condensing equipment.

2. The Rooftop Inducer was tested with exit flue gas temperatures of 1000

O

F (537

O

C) U.S. and 575

O

F (300

O

C) Canada.

3. The Rooftop Inducer may not be installed on incinerators or incinerating toilets.

4. The Rooftop Inducer must always be installed at the vent system termination. Not suitable for Side Wall terminations.

5. The Rooftop Inducer shall not be installed on an appliance with an automatic valve having a manual opener unless the manual

opener has been rendered inoperative or the automatic valve has been replaced with a valve not equipped with a manual opener.

6. RT750 / RT1500 Rooftop Inducers may only be installed on appliances equipped with a draft hood, draft diverter, barometric

draft control or other dilution air providing source.

The Rooftop Inducer is designed to fit any type of nominal (8" Models RT750 / RT750H) or (12" Models RT1500 / RT1500H) diame-
ter vent pipe. Vent pipe must be installed and supported according to manufacturer's instructions and/or in accordance with NFPA 211,
"Chimneys and Vents". Factory insulated vent pipe may reduce clearances to combustibles when penetrating a combustible roof.
Refer to vent pipe manufacturer's instructions for details.

INSTALLER CAUTIONS

Disconnect the power supply when making wiring connections or when working around the Inducer impeller and motor. Failure to do
so can result in electrical shock, personal injury, death or property damage.

1. The model PSA-1 Fan Proving Switch provided must be interlocked with the heating appliance burner(s).

2. Plan the vent system so that the code required clearances are maintained from plumbing, wiring and combustibles.

3. Make certain the power supply is adequate for Rooftop Inducer motor requirements. Do not add the Rooftop Inducer to a circuit

where the total load is unknown.

4. The installer must verify that the appliance(s) on which the Rooftop Inducer will be installed is in a safe operating condition. Consult

appliance manufacturer's Instructions for details.

5. Rooftop Inducer housing is single wall. Standard clearances to combustibles must be maintained.

CONDITIONS D'INSTALLATION

Ne pas installer, entretenir et(ou) utiliser le Système d'admission d'air pour toit conformément aux directives du fabricant pourrait
entraîner des circonstances qui causeront des blessures et endommageront la propriété.

Le Système d'admission d'air pour toit doit être installé par un installateur qualifié conformément aux présentes directives et à toutes
les normes applicables à la localité. En l'absence de normes locales au Canada, les installations doivent respecter le Code canadien
de l'électricité (CSA Std 22.1), la dernière version du Code d'installation du gaz naturel (CAN/CGA-B149.1), le Code d'installation du
propane (CAN/CGA-B149.2) et le Code d'installation des appareils de combustion au mazout (CSA Std B139-M91).

Une installation inadéquate pourrait entraîner un danger, comme une explosion, un feu, une décharge électrique ou un empoison-
nement au monoxyde de carbone qui endommagera la propriété, occasionnera des blessures ou même la mort.

1. Le Système d'admission d'air pour toit peut être installé sur des systèmes de chauffage aux gaz naturels, aux gaz de pétroles

liquéfiés, au mazout ou aux combustibles solides ou systèmes de ventilation générale. Le Système d'admission d'air pour toit ne
convient pas aux systèmes de condensation.