CCI Thermal Technologies CWCB - Packaged Circulation Heater Manuel d'utilisation

Page 2

Advertising
background image

2.7.4 a pressure relief valve is a safety feature which is intended to

open when the system malfunctions or is improperly operated or

maintained. unites equipped with a pressure relief valve should

be fitted with piping to direct the discharge down and away from

personnel or equipment. neVer install a sHut oFF ValVe

on eitHer siDe oF a Pressure relieF ValVe.

2.7.5 optional expansion tank (for closed loop systems) is mounted in

the outlet piping.

2.7.6 A 1½" NPT drain plug is fitted at the bottom of the heater. We

recommend use of a drain valve to simplify clean-out of sludge

which may accumulate in the vessel. sludge build-up can cause

heating element failure.

2.7.7 For flow rates greater than 50 gpm, to reduce tank erosion, a

bypass loop with regulating valve is recommended.

2.7.8 Closed loop systems require an air bleed valve, preferably

installed at the highest point in the piping loop.

3.0 START UP AND OPERATION

3.1

the CW heater is designed to heat water in a non-hazardous

environment. in some closed loop systems chemically stabilized

ethylene glycol may be added to the water for freeze protection or

toe elevate the boiling point. if you are unsure as to suitability of

glycol to your heating loop contact the factory.

3.2

Check the electrical system for the loose connections and tighten

if required.

3.3

after all piping is installed turn the thermostat to its lowest setting

and operate the circulating pump for up to 1/2 hour to check for

leaks and to remove air pockets. in closed loop systems use the

air bleed valve to remove entrapped air. an air lock in the heater

vessel could cause the heaters to run dry and fail prematurely.

3.4

set the thermostat to the desired temperature. the temperature

rise through the unit will depend on the flow rate and the heater

kilowatt (Kw) rating.

For water: GPM

imp

=

example: For a 30 Kw heater and a 10 °F temperature rise the

flow required in imperial gallons per minute is:

GPM

imp

=

= 17

adjust the thermostat differential to give the desired cycling rate.

it is best to use the maximum acceptable differential so as to

minimize cycling and prolong component service life. However, if

the system requires close control a narrow differential setting will

be necessary.

3.5

For systems using a bypass loop, open the bypass valve to

reduce the load on the pump but not enough to cause the limit

thermostat to open. For pool heating, the ideal bypass opening

will result in water leaving the heater at not more than 90 °F.

5.69 Kw

temp. rise (°F)

(5.69)(30)

10

3.6 the built-in temperature high limit is factory set at 180°F (82°C).

this control works best when it is set about 40°F (22°C) above

the water outlet temperature. to adjust the limit control setting

remove the small panel on the limit control to access the

adjustment screw. under normal operation the heater should not

cycle on the limit control.

3.7 if the limit trips it must be manually reset before the heater will

operate. Prior to reset, the condition(s) which caused the trip shall

be corrected.

4.0 MAINTENANCE

4.1 service to the unit shall only be done when the power is

disconnected at the mains.

4.2 After the first few days of operation, and periodically thereafter,

inspect for piping leaks and loose electrical connections.

4.3 the CWCB-XXX-2 unit, because it is used in an open loop water

heating system, may be subject to sludge build-up if the water is

hard and untreated. this unit must be drained at regular intervals

(depending on water conditions and operating time to remove

sludge. Once a year a flange heater must be removed and the

vessel inspected and cleaned as required. local conditions may

cause the inspection time to vary.

Advertising