INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3 – INFRARED RADIANT HEATERS

FIRE/EXPLOSION HAZARD WARNING - During operation, take precautions to ensure that

combustible materials are always kept at a safe distance from the radiant energy. This heater is

not intended for use in hazardous areas where flammable vapours, gases or liquids or other

combustibles are present. Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures. If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations. Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion. The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage. Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum space clearances from combustibles, when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the safety of this equipment and

adequate back-up controls and safety

devices must be installed. Failure to

comply could result in personal injury

and/or property damage.

Heaters must be wired by qualified

personnel in compliance with local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply. Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation contamination or moisture

accumulation can cause fault to the

element sheath generating arcing and

releasing molten metal. Install proper

ground fault protection to prevent

personal injury and/or property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply conductors to the heater must be suitable for

110°C(230°C). The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1". The standard Type 1 enclosure

is suitable for dry, indoor locations only in non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes located at each top corner of the housing. Either chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support (slotted holes) is adequate provided that the spacing

instructions as given in 3.0 are followed. Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

cm

[12”

]

FIG. 1 – MOUNTING CLEARANCES

ISO 9001

MI182 REV.8.01 Page 1 of 2

MI182 REV.8 Page 1 of 2

CCI Thermal Technologies Inc. 2721 Plymouth Drive, Oakville, ON L6H 5R5 Tel. (905) 829-4422 Fax (905) 829-4430

www.ccithermal.com

ISO 9001:2000

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3 – INFRARED RADIANT HEATERS

FIRE/EXPLOSION HAZARD WARNING - During operation, take precautions to ensure that

combustible materials are always kept at a safe distance from the radiant energy. This heater is

not intended for use in hazardous areas where flammable vapours, gases or liquids or other

combustibles are present. Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures. If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations. Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion. The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage. Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum space clearances from combustibles, when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the safety of this equipment and

adequate back-up controls and safety

devices must be installed. Failure to

comply could result in personal injury

and/or property damage.

Heaters must be wired by qualified

personnel in compliance with local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply. Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation contamination or moisture

accumulation can cause fault to the

element sheath generating arcing and

releasing molten metal. Install proper

ground fault protection to prevent

personal injury and/or property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply conductors to the heater must be suitable for

110°C(230°C). The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1". The standard Type 1 enclosure

is suitable for dry, indoor locations only in non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes located at each top corner of the housing. Either chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support (slotted holes) is adequate provided that the spacing

instructions as given in 3.0 are followed. Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

cm

[12”

]

FIG. 1 – MOUNTING CLEARANCES

FIRE/EXPLOSION HAZARD WARNING - During operation, take precautions to ensure that combustible

materials are always kept at a safe distance from the radiant energy. This heater is not intended

for use in hazardous areas where flammable vapours, gases or liquids or other combustibles are

present. Remember that objects placed under an infrared heater can take a while to reach stabilized

temperatures. If you are unsure of the suitability of the heater for the intended application, check

with the factory for recommendations. Failure to comply can result in personal injury and/or property

damage.

1.0 The OK3 radiant heaters are suitable for comfort heating use

in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion. The heater does

not present a safety hazard when it is installed, operated and

maintained in accordance with these instructions.

2.0 The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending

on voltage. Never change heaters which have been factory series

connected to a parallel connection.

3.0 Minimum space clearances from combustibles, when heaters

are horizontally mounted and installed, as listed in Table 1 following.

DESCRIPTION

MI182 REV.8 Page 1 of 2

CCI Thermal Technologies Inc. 2721 Plymouth Drive, Oakville, ON L6H 5R5 Tel. (905) 829-4422 Fax (905) 829-4430

www.ccithermal.com

ISO 9001:2000

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3 – INFRARED RADIANT HEATERS

FIRE/EXPLOSION HAZARD WARNING - During operation, take precautions to ensure that

combustible materials are always kept at a safe distance from the radiant energy. This heater is

not intended for use in hazardous areas where flammable vapours, gases or liquids or other

combustibles are present. Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures. If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations. Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion. The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage. Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum space clearances from combustibles, when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the safety of this equipment and

adequate back-up controls and safety

devices must be installed. Failure to

comply could result in personal injury

and/or property damage.

Heaters must be wired by qualified

personnel in compliance with local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply. Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation contamination or moisture

accumulation can cause fault to the

element sheath generating arcing and

releasing molten metal. Install proper

ground fault protection to prevent

personal injury and/or property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply conductors to the heater must be suitable for

110°C(230°C). The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1". The standard Type 1 enclosure

is suitable for dry, indoor locations only in non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes located at each top corner of the housing. Either chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support (slotted holes) is adequate provided that the spacing

instructions as given in 3.0 are followed. Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

cm

[12”

]

FIG. 1 – MOUNTING CLEARANCES

4.0 To facilitate mounting, the heater has four ¼”-20 mounting

holes located at each top corner of the housing. Either chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support (slotted holes) is adequate provided that the spacing

instructions as given in 3.0 are followed. Chain mounting is

preferred since rigidly mounted heaters are susceptible to warping.

The system designer is responsible for the safety

of this equipment and adequate back-up controls

and safety devices must be installed. Failure to

comply could result in personal injury and/or

property damage.

Heaters must be wired by qualified personnel in

compliance with local codes.

5.0 Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply. Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation contamination or moisture accumulation

can cause fault to the element sheath generating

arcing and releasing molten metal. Install proper

ground fault protection to prevent personal injury

and/or property damage.

6.0 The connection box volume is 3100 cm³(190 in³).

7.0 Supply conductors to the heater must be suitable for

110°C(230°C). The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0 The connection box has eight dual knockouts, ½” or ¾” and two

dual knockouts ¾” or 1”. The standard Type 1 enclosure is suitable

for dry, indoor locations only in non-corrosive environments.

9.0 For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

10.0 To maximize heating efficiency, periodically wipe clean the

reflector with a cloth dampened with alcohol.

INSTALLATION