Watts FS10-C Manuel d'utilisation

Flow switch fs10-c series, Important, Flow rates for these sizes are calculated

Advertising
background image

MIN 5 X D

APPROXIMATELY 1"

USE HALF COUPLING

MIN 5 X D

D

REPLACEMENT

KIT NUMBER DESCRIPTION

RK FS10-3-1 PADDLE A, B & C

RK FS10-6 PADDLE D

RK PRP-218-3957 “O” RING

USA: 815 Chestnut St., North Andover, MA 01845-6098

www.watts.com

CANADA: 5435 North Service Rd., Burlington, Ont. L7L 5H7

www.wattscanada.ca

FLOW SWITCH FS10-C SERIES

GENERAL APPLICATION: AUTOMATIC CONTROL AND SAFETY DEVICE, NOT INTENDED FOR FIRE SPRINKLER SYSTEMS.

— Principally used in water systems, heating systems, air conditioning and processing installations.
— Single pole double throw switch can be wired to make one circuit or break a circuit when flow starts or stops.
— Actuates an alarm when flow is inadequate — deactivates alarm when sufficient flow is restored.
— Parts in contact with liquid in pipe are of brass and beryllium copper.

IMPORTANT:
Electrical installation must be performed by a qualified person and in accordance with all local codes.

LOCATION: Flow switch should be installed in horizontal or vertical section of a pipe or tube where there is a straight run of at least 5
pipe diameters on each side.

MOUNTING: Flow switch should be installed vertically upright in tees or welded fittings.

If a reducing tee is not available and a standard tee

is used, install a face bushing in top opening to

keep waterflow indicator as close to tee as possible.

If a welded fitting is to be used, use only a half

coupling. (Make sure hole in main is 1-5/32" dia.

before welding coupling.)

NOTE: PADDLE LENGTH CONFORMS TO

ASTM TEE STANDARD.

USE PROVIDED TEMPLATE TO TRIM

PADDLE TO REQUIRED LENGTH “L”.

ACTUAL SIZE TEMPLATE TO TRIM DIMENSION “L”

Always check operation of flow switch to make sure paddle

is free to move in the tee, coupling or pipe before finishing

the installation.

“L” refers to trim length in table.

UNDERWRITER’S LABORATORY LISTED

MAXIMUM PRESSURE 175 PSI

MAXIMUM TEMPERATURE 300ºF

A. FINE SENSITIVITY

1. REMOVE SWITCH COVER.

2. FOR FINER SENSITIVITY, TURN

RANGE ADJUSTING SCREW

CLOCKWISE. LOCATED ON

LEVER NEXT TO MICROSWITCH.

B. COARSE SENSITIVITY

1. REMOVE SWITCH COVER.

2. FOR HIGHER FLOW RATE, TURN

RANGE ADJUSTING SCREW

CLOCKWISE. LOCATED WITH

ADJUSTING SPRING.

3. FOR LOWER FLOW RATE, TURN

COUNTER CLOCKWISE.

ADJUSTMENT

TO ADJUST SETTINGS, FOLLOW

A OR B INSTRUCTIONS. BE

SURE FLOW SWITCH COVER IS

REPLACED BEFORE LEAVING

JOB.

PIPE

SIZE

INSTALLATION USING

ASTM TEE

INSTALLATION USING

WELDED FITTING

PADDLE

TEE SIZE

PADDLE

1”

1” x 1” x 1”

1”A Segment

1-1/4”

1-1/4” x 1-1/4” x 1”

1”A Segment &

Trimmed

2”B Segment

1-5/8”

1-1/2”

1-1/2 x 1-1/2” x 1”

1”A Segment &

Trimmed

2”B Segment

1-3/4”

2”

2” x 2” x 1”

1”A Segment &

2” B Segment

1”A Segment & 2”B Segment

2-1/2”

2-1/2” x 2-1/2” x 1”

1”A & 2”B

Segments &

Trimmed 3”C

Segments

1”A & 2”B Segments &

Trimmed 3”C Segments

2-3/4”

3”

3” x 3” x 1”

1”A, 2”B, & 3”C

Segments

1”A, 2”B, & 3”C Segments

4”

1”A, 2”B, 3”C, and

Trimmed 4”D Segments

4-1/4”

5”

1”A, 2”B, 3”C, and

Trimmed 4”D Segments

5-1/4”

6”

1”A, 2”B, 3”C, 4”D Segments

TRIMMED

DIMENSION

“L”

IMPORTANT:

Mount flow switch in position so that the paddle assembly is at a right angle to the flow. The stamped arrow on bottom plate mounting and top cover gum label arrow must
both point in direction of flow.

1-1/8”

1-

3/

4”

1-5/8”

2-1/8”

2-3/4”

3-1/4”

4-1/4”

5-1/4”

6-1/4”

FLOW

FLOW RATES REQUIRED TO ACTUATE No. FS10-C FLOW SWITCH IN HORIZONTAL PIPE

Flow rates in U.S. gallons per minute (GPM). Velocity in feet per second (FPS).

*Equipped with extended paddle trimmed to pipe size

FINE

SENSITITY

ADJUSTMENT

COARSE

SENSITITY

ADJUSTMENT

*Flow rates for these sizes are calculated.

PADDLE LENGTH: Included with each flow switch are four paddles. Shortest paddle (A) can be used for 1" pipe size only.

Second shortest paddle (B) can be used as is with paddle (A) for 2" pipe size; but must be trimmed for 1- 1/4" and 1-1/2" pipe size.

Third shortest paddle (C) can be used as is with paddle (A) and (B) for 3" pipe size, but must be trimmed for 2-1/2" pipe size.

Longest paddle (D) can be used as is with paddle (A), (B) and (C) for 6" pipe size, but must be trimmed for 4" and 5" pipe size.

(A)

(B)

(C)

(D)

 

¡

 

¢

£¤

¥

¡

 

¢

£ ¤

¦

¡

 

¢§

¤

¨

¡

 

¢§

¤

Extended
Paddle

Pipe Size in Which

Flow Switch Installed

1”

1-1/4”

1-1/2”

2”

2-1/2”

3”

*4”

*5”

*6”

Factory or

Minimum

Flow Setting

ACTIVATION

FLOW

GPM

5.2

7.9

10.0

13.2

20.9

30.0

39.0

58.0

79.9

FPS

2.01

1.74

1.62

1.29

0.92

1.30

1.0

0.94

0.88

DEACTIVATION

GPM

2.0

3.2

5.3

8.1

9.9

12.0

19.0

29.0

39.6

FPS

0.77

0.71

0.86

0.79

0.44

0.52

0.50

0.47

0.44

Maximum

Flow Setting

ACTIVATION FLOW

GPM

11.5

18.0

18.0

34.1

53.9

52.0

73.5

115.0

166.0

FPS

4.44

3.98

2.91

3.33

2.38

2.26

1.86

1.85

1.84

GPM

8.5

14.6

15.1

29.2

44.4

46.1

64.0

92.0

123.0

FPS

3.28

3.23

2.44

2.85

1.96

2.00

1.67

1.48

1.37

DEACTIVATION

Extended

Paddle

IS-FS10-C

EDP# 5003170 rev 5

!!

"

#

$

% & '

% & '

(

)

(

(

) * ) +

) +

, !

- " ! " -. /

+ 0 % " - '

1 )

+

&

" - .

# #

)

(

+ , +

(

, ) +

) ,

2

*

+

) ,

2

*

+

3 0 . 1! 3

'

3 0 . .

1! 3

'

OPTIONS:

“L” Pilot Light

“BSP” British Threaded Body

REPAIRS AND REPLACEMENT

PADDLES AND COVER MAY BE REPLACED IN THE FIELD. OTHER FIELD REPAIRS MUST NOT BE MADE. REPLACEMENT FLOW SWITCHES MAY BE

OBTAINED FROM THE NEAREST WATTS DISTRIBUTOR OR WHOLESALER. WHEN ORDERING A REPLACEMENT SWITCH, SPECIFY PRODUCT NUMBER

AS SHOWN ON THE FLOW SWITCH.

Advertising