Appendix B 1769 DeviceNet Modules Status Indicators and Data Structures

Table 13 - Network Status Indicator

Indicator Condition

Description

Off

One of these conditions exists:

The scanner is not powered.

The network is not powered.

Communication is not occurring between the scannner and the

DeviceNet network. (This may be an acceptable condition.)

Complete these steps to change this state.
1. Verify that the scanner has power.
2. Check that the DeviceNet cable is securely connected and the

DeviceNet network is powered.

3. Verify that network power is adequate (11…25V DC).

Flashing green

The scanner is fully operational, but there are no connections
established with any of the devices on the network.
If the scannner should be controlling DeviceNet slaves, configure its
scan list.

Solid green

The scanner is fully operational and communicating with the
controller.

Flashing red

One or more of the devices that the scanner is communicating with is
in a timed-out state.
Monitor the status display to determine which slave device is offline.

Solid red

A critical network failure has occurred because a duplicate DeviceNet
node address has been detected.
Reset the scannner and change the node address of either the
scanner or that of the conflicting device. If the failure continues,
replace the scanner.