Rockwell Automation Publication ENMON-IN320H-EN-P - February 2014

9

XM-320 Position Module

Reset Switch

The XM-320 module has an external reset switch on top of the module. The Reset switch can be used to reset all latched
relays, including the relays in the Relay Expansion module when it is attached to the XM-320 module.

Install the XM Serial Configuration Utility Software

The XM Documentation and Configuration Utility CD is packaged with the XM modules. It contains the XM Serial
Configuration Utility software, a set of user guides, hazardous location installation drawings, and electronic data sheet
(EDS) files that are used by network configuration tools such as RSNetWorx™ for DeviceNet software. The user guides are
in portable document format (PDF), and must be viewed with Adobe Acrobat Reader software.

To install the XM Serial Configuration Utility software, follow these steps.

1. Insert the XM Documentation and Configuration Utility CD-ROM into the CD-ROM drive.

2. Follow the instructions that appear to install the XM Serial Configuration Utility.

3. When you are finished installing the software, remove the XM Documentation and Configuration Utility

CD-ROM from the CD-ROM drives; store it in a safe place.

IMPORTANT

The Reset switch resets the relays only if the input is no longer in alarm or the condition that caused the alarm is no longer
present.

If autorun is

Then

Enabled

The Setup program starts automatically and the XM Serial Configuration Utility opening screen appears.

Disabled

Follow these steps.
1. Click Start, and then click Run.

The Run dialog box appears.

2. In the Open box, type

x:\autorun, where x is the letter of the drive containing the XM Documentation and

Configuration Utility CD-ROM.

3. Click OK.

The XM Serial Configuration Utility opening screen appears.

POSITION

1440-TPS02-01RB

Reset Switch