Rockwell Automation Publication ENMON-IN320H-EN-P - February 2014

XM-320 Position Module

Channel 1 and Channel 2 Status Indicator

Setpoint Multiplier Indicator

Relay Indicator

Self-Test

The XM-320 module performs a self-test at powerup. The self-test includes a status indicator test and a device test. During
the status indicator test, the indicators are turned on independently and in sequence for approximately 0.25 seconds.

The device test occurs after the status indicator test. The Module Status (MS) indicator is used to indicate the status of the
device self-test.

Color

State

Description

No color

Off

Normal operation with alarm limits on the channel.
No power applied to the module; look at Module Status indicator.

Yellow

Solid

An alert level alarm condition exists on the channel (and no transducer fault or danger level alarm condition exists).

Red

Solid

A danger level alarm condition exists on the channel (and no transducer fault condition exists).

Flashing

A transducer fault condition exists on the channel.

Color State

Description

Yellow

Off

Setpoint multiplier is not in effect.

Solid

Setpoint multiplier is in effect.

Color

State

Description

Red

Off

On-board relay in not activated.

Solid

On-board relay is activated.

MS Indicator State

Description

Flashing red and green

Device self-test is in progress.

Solid green or flashing green

Device self-test completed successfully, and the firmware is valid and running.

Flashing red

Device self-test completed, the hardware is OK, but the firmware is invalid. Or, the firmware download is in progress.

Solid red

Unrecoverable fault, hardware failure, or Boot Loader program corruption.