Rockwell Automation 1769-PB4 Compact I/O Expansion Power Supplies Manuel d'utilisation

Page 32

Advertising
background image

32 Compact I/O Expansion Power Supplies

Publication 1769-IN028B-EN-P - October 2008

Vibration

IEC 60068-2-6 (Test
Fc, Operating)

5 g @ 10…500 Hz

Operating shock

IEC 60068-2-27
(Test Ea,
Unpackaged Shock)

DIN rail mount: 20 g; Panel Mount 30 g

Nonoperating
shock

IEC 60068-2-27
(Test Ea,
Unpackaged Shock)

DIN rail mount: 30 g; Panel Mount 40 g

Emissions
CISPR 11

Group 1, Class A

ESD immunity
IEC61000-4-2

4 kV contact, 8 kV air discharges

Radiated RF
immunity
IEC61000-4-3

10V/m with 1 kHz

sine-wave 80%

AM from 80…2000

MHz

3V/m with 1 kHz

sine-wave 80%

AM from

2000…2700 MHz

10V/m with 200 Hz

50% Pulse 100%

AM at 900 MHz

10V/m with 200 Hz

50% Pulse 100%

AM at 1890 MHz

10V/m with 1 kHz

sine-wave 80%AM

from 80…2000

MHz

10V/m with 200 Hz

50% Pulse

100%AM at 900

MHz

10V/m with 1 kHz

sine-wave 80%

AM from 80…2000

MHz

3V/m with 1 kHz

sine-wave 80%

AM from

2000…2700 MHz

10V/m with 200 Hz

50% Pulse 100%

AM at 900 MHz

10V/m with 200 Hz

50% Pulse 100%

AM at 1890 MHz

10V/m with 1 kHz

sine-wave 80%AM

from 80…2000

MHz

10V/m with 200 Hz

50% Pulse

100%AM at 900

MHz

EFT/B immunity
IEC 61000-4-4

+2 kV at 5 kHz on

AC power ports

±2 kV at 5 kHz on

24V DC PWR OUT

ports

+2 kV at 5 kHz on

DC power ports

+2 kV at 5 kHz on

AC power ports

+2 kV at 5 kHz on

DC power ports

Surge transient
immunity
IEC61000-4-5

±2 kV line-line (DM)

and ±4 kV line-earth

(CM) on AC power

ports

±500V line-line
(DM) and ±500V
line-earth (CM) on
24V DC PWR OUT
ports

±500V line-line (DM)

and ±500V

line-earth (CM) on

DC power ports

±2 kV line-line (DM)

and ±4 kV line-earth

(CM) on AC power

ports

±500V line-line (DM)

and ±500V

line-earth (CM) on

DC power ports

1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4 - Environmental Specifications

Attribute

1769-PA2

1769-PB2

1769-PA4

1769-PB4

Advertising