Schematic (using ansi/csa symbols), Connect the power supplies – Rockwell Automation 1769-PB4 Compact I/O Expansion Power Supplies Manuel d'utilisation

Page 19

Advertising
background image

Compact I/O Expansion Power Supplies 19

Publication 1769-IN028B-EN-P - October 2008

Schematic (Using ANSI/CSA Symbols)

Connect the Power Supplies

Compact I/O system architecture and the power supply design support connection of I/O
on either side of the power supply. Each I/O bank requires its own power supply.

To connect 2 I/O banks, attach a 1769 expansion I/O cable to a power supply or I/O
module as shown in the

Power Supply Connection

illustration. Up to 8 I/O modules can be

connected on either side (A or B in the illustration) of the power supply for a maximum of 16
modules per bank.

L1

L2

Disconnect

Isolation
Transformer

X1

X2

Fuse

Operation of either of these
contacts will remove power from
the external I/O circuits, stopping
machine motion.

Emergency-Stop
Push Button

Overtravel
Limit Switch

Stop

Start

Fuse

MCR

230V AC
I/O

Circuits

Master Control Relay (MCR)
Cat. No. 700-PK400A1

Suppressor
Cat. No. 700-N24

MCR

Suppr

MCR

MCR

115V AC or
230V AC

DC Power Supply.
Use NEC Class 2 for
UL Listing.

_

+

24V DC

I/O Circuits

MCR

(Lo)

(Hi)

230V AC

Line Terminals: Connect to the 24V
DC 1769 power supply terminals.

Line Terminals: Connect to the AC
1769 power supply terminals.

115V AC

or 230V

AC

Advertising