1769-iq6xow4 configuration file – Rockwell Automation 1769-IQ6XOW4 Compact Combination 24V dc Sink/Source Input AC/DC Relay Output Module Manuel d'utilisation

Page 12

Advertising
background image

12 Compact™ Combination 24V dc Sink/Source Input & AC/DC Relay Output Module

Publication 1769-IN050A-EN-P - April 2001

For the 1769-IQ6XOW4, bits 4 to 15 are not used.

r = read

1769-IQ6XOW4 Configuration File

The read/writable configuration data file allows the setup of the hold last state and
user-defined safe state conditions.

The manipulation of the bits from this file is normally done with programming
software (e.g. RSLogix 500, RSNetworx for DeviceNet, etc.) during initial
configuration of the system. In that case, graphical screens are provided via the
programmer to simplify configuration. However, some systems (e.g. 1769-ADN
DeviceNet Adapter) also allow the bits to be altered as part of the control program
using communication rungs. In that case, it is necessary to understand the bit
arrangment.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

0

0

0

0

0

0

r

r

r

r

r

r

1

0

0

0

0

0

0

0

0

0

0

0

0

r

r

r

r

IMPORTANT

Input data file word 1 reflects the output data echo of the
module, not necessarily the electrical state of the output
terminals. It does not reflect shorted or open outputs.

It is important to use this input word if the controller adapter
supports the Program Mode or Fault Mode function, and if it is
configured to use them.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

PFE

1

Program State for Output Array Word 0

2

Program Value for Output Array Word 0

3

Fault State for Output Array Word 0

4

Fault Value for Output Array Word 0

Advertising