XM-124 Standard Dynamic Measurement Module 9

Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

Terminal Block Assignments

No.

Name

Description

0

Xducer 1 (+)

Vibration transducer 1 connection

1

Xducer 2 (+)

Vibration transducer 2 connection

2

Buffer 1 (+)

Vibration signal 1 buffered output

3

Buffer 2 (+)

Vibration signal 2 buffered output

4

Tach/Signal In (+)

Tachometer transducer/signal input, positive side

5

Buffer Power 1 IN

Channel 1 buffer power input
Connect to terminal 6 for positive bias transducers or terminal 21 for
negative bias transducers

6

Positive Buffer Bias

Provides positive (-5...24V) voltage compliance to buffered outputs
Connect to terminals 5 (CH 1) and 22 (CH 2) for positive bias transducers

7

TxD

Personal computer serial port, transmit data

8

RxD

Personal computer serial port, receive data

9

XRTN

1

Circuit return for TxD and RxD

10

Chassis

Connection to DIN-rail ground spring or panel mounting hole

11

4-20 mA 1 (+)

4…20 mA output
300

Ω maximum load

12

4-20 mA 1 (-)

13

Chassis

Connection to DIN-rail ground spring or panel mounting hole

14

Chassis

Connection to DIN-rail ground spring or panel mounting hole

15

Chassis

Connection to DIN-rail ground spring or panel mounting hole

16

Xducer 1 (-)

1

Vibration transducer 1 connection

17

Xducer 2 (-)

1

Vibration transducer 2 connection

18

Signal Common

1

Vibration buffered output return

19

TACH Buffer

Tachometer transducer/signal output

20

Tachometer (-)

Tachometer transducer/signal return, TACH Buffer return