18 XM-124 Standard Dynamic Measurement Module

Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

DIP Switch Functions and Defaults

Switch

Purpose

Function

Out-of-box
Default
Value

Out-of-box
Switch
Setting

1

DIP switch
disable

Determines whether DIP switches 3…10
are enabled. When this switch is in the off
position, DIP switches 3…10 set the
module’s node address and communication
rate. When the switch is on, the device
ignores DIP switches 3…10 and uses the
network address and communication rate
programmed in nonvolatile storage.

Switches
enabled

Off

2

Network
mode

Sets the DeviceNet behavior of the module
to either Normal mode (ODVA compliant) or
Legacy mode, which is consistent with
earlier XM module versions.

Normal (fully
compliant)

On

3, 4

Data rate

When switch 1 is off (0), the DeviceNet
communication rate is set.

125 Kbps

Both off

5…10

Node
address

When switch #1 is off (0), the DeviceNet
node address is set.

63

All on