18 XM-124 Standard Dynamic Measurement Module
Rockwell Automation Publication 1440-IN001B-EN-P - October 2013
DIP Switch Functions and Defaults
Switch
Purpose
Function
Out-of-box
Default
Value
Out-of-box
Switch
Setting
1
DIP switch
disable
Determines whether DIP switches 3…10
are enabled. When this switch is in the off
position, DIP switches 3…10 set the
module’s node address and communication
rate. When the switch is on, the device
ignores DIP switches 3…10 and uses the
network address and communication rate
programmed in nonvolatile storage.
Switches
enabled
Off
2
Network
mode
Sets the DeviceNet behavior of the module
to either Normal mode (ODVA compliant) or
Legacy mode, which is consistent with
earlier XM module versions.
Normal (fully
compliant)
On
3, 4
Data rate
When switch 1 is off (0), the DeviceNet
communication rate is set.
125 Kbps
Both off
5…10
Node
address
When switch #1 is off (0), the DeviceNet
node address is set.
63
All on