Specifications spécifications, Technische daten specifiche especificaciones, I/o wiring data – Rockwell Automation 1492-AIFM8-F-5 8 Channel Fusible Analog Input Interface Module Manuel d'utilisation

Page 6

Advertising
background image

Specifications
Spécifications

Reference Publications: Refer to 1770-4.1 and appropriate PLC I/O module installation manual.

0.85 lb.

385 g.

Maximum Recurring Peak Voltage

Tension de crele réurrente maximale

Maximale periodische Hochstspannung

Tensione massima di cresta ricorrente

Voltaje de cresta iterativo máximo

600 V

p

4.72 in. (120 mm) W

3.27 in. (83 mm) H

2.74 in (69.5 mm) D

cULus (File: E10314, Guide No. NRAG)

Suitable for use in Class 1 Div 2 Groups A,

B, C and D Hazardous and Non-Hazardous

Locations.

Temperature Code = T3C at 60°C

CE: Compliant for all applicable directives

FM Class 1 Div 2 Groups A, B, C and D

Temperature Rating T3C = 60°C (J.I. 3000590,

all except relay modules)

< 2.0 mA

0° C - 60° C

Indicator Circuit Current

Courant circuit voyants

Strom, Anzeigeschaltkreis

Corrente circuito indicatori

Intensidad del circuito de
indicadores

Voltage

Tension

Spannung

Tensione

Voltaje

Catalog No.

Référence

Bestell-Nr.

N. Catalogo

Referencia

Technische Daten
Specifiche

Especificaciones

Dimensions

Dimensions

Abmessungen

Dimensioni

Dimensiones

Approx. Shipping Weight

Poids d'embarquement approximatif

Ungefähres Versandgewicht

Peso approssimativo del carico

Peso aproximado al momento de
embarque

Standards

Normes

Standards

Standard

Estándares

Catalog No.

Référence

Bestell-Nr.

N. Catalogo

Referencia

Operating Temperature Range

Plage températures de fonctionnement

Betriebstemperaturbereich

Limiti temperatura di funzionamento

Rango de temperatura de funcionamient

Current/Circuit

Courant/Circuit

Strom/Schaltkreis

Corrente/circuito

Intensidad/circuito

Current/Module

Courant/Module

Strom/Modul

Corrente/modulo

Intensidad/módulo

2 Amps

12 Amps

1492-AIFM8-F-5

1492-AIFM8-F-5

10-30 VAC/DC

5 - 95%

Operating Humidity

Humidité relative

Betriebsluftfeuchtigkeit

Umidità di esercizio

Humedad operativa

For transients > 600 Vp use a UL recognized suppression device rated at 2.5 kV withstand.

Pour des transitoires > 600 Vp utilisez un dispositif de suppression certifié UL à 2,5 kV nominal de tenue.
Für Einschaltstöße > 600 Vp verwenden Sie einen UL anerkannten Entstörer, der bewertet wurde bei 2,5 kV standzuhalten.
Per transitori > 600 Vp usare dispositivo di soppressione riconosciuto da UL capace di sopportare 2,5 kV.
Para transitorios > 600 Vp use un dispositivo de supresión reconocido UL clasificado con 2,5 kV.

Non-condensing

Sans condensation
Nicht kondensierend
Senza condensa
sin condensación

Power, input and output (I/O) wiring must be in accordance with Class I Division 2 wiring methods - Artticle 501-10(B)(1) of the National Electrical Code.

WARNING

Explosion Hazard - substitution of components may impair suitability for Class I Division 2.
Explosion Hazard - Do Not Disconnect Equipment unless power has been switched off or the area is known to be Non-Hazardous.

SURGE SUPPRESSION follow the literature recommendations of the PLC module being used.
SUPPRESSION DES SURTENSIONS se trouve à la suite de la littérature qui contient les recommandations relatives au module PLC utilisé.
ÜBERSPANNUNGSSCHUTZ Bitte beachten Sie die Dokumentationsempfehlungen für das jeweils benutzte SPS-Modul.
Per la SOPPRESSIONE DEI PICCHI TEMPORANEI, seguire le istruzioni riportate nella documentazione in dotazione al Modulo PLC utilizzato.
SUPRESIÓN DE SOBRETENSIÓN, siga las recomendaciones indicadas en la documentación del módulo PLC respectivo.

I/O Wiring Data

NOTICE

Wiring information for your I/O module, AIFM module and cable (e.g. wiring diagram and pinouts)are available online at www.rockwellautomation.com/en/e-tools.
To obtain information follow this procedure.
1) In the Catalog Number BOX at the above online site type in the catalog number of the IFM, AIFM, etc. module you are using and click on Submit.
2) At the next screen displayed, click on the Modify key (lower left of screen).
3) Click on the areas that indicate NO SELECTION and enter your specific configuration information (e.g. I/O platform, I/O MODULE, ETC.).
NOTE: To obtain the wiring diagram, you must select th Pre-Wired Cable Connector selection.
4) Configure your 1492 cable by filing in the NO SELECTION areas.
5) Click on the ACCEPT key for the configured 1492 cable. At the next screen click on ACCEPT for the 1492 module.
6) The next screen (Configuration Results) displays the results of your specific configuration. The "supplementary Documents" column contains I/O wiring information
for the configuration (e.g. I/O Wiring Diagrams).

PN-23244
DIR 40063-320 (Version 11)

Printed in U.S.A.