Bulletin 836t pressure controls, Piston type shown

Advertising
background image

Differential

Pressure Adjustment

Screw "B"

(through access opening)

Differential

Pressure Adjustment

Screw "B"

Operating Range

Adjustment

Screw "A"

Pilot Light

Receptacle

Upper Pressure

Setting Indicator

1/4" - 18 N.P.T.F.

3/8" - 18 N.P.T.F.

or Optional Threads

Pressure

Connection

Locking Nut

Operation

Indicator

(Bellows

Type Only)

Electrical

Hub Connection

Bulletin 836T

Bellows Type Control

2 - Circuit

Bulletin 836T Piston Type

Shown With Cover Removed

Pressure

Connection

Ground

Screw

Contact

Block

Bulletin 836T Pressure Controls

DESCRIPTION - Bulletin 836T, Type 1, 4, & 13 oiltight pressure con-
trols are designed for use on machine tool applications where a stream of
oil or water may flow over the enclosure. Other applications would include
areas where it is desirable to resist the entrance of lint, dust, and dirt into
the enclosure.

The operating range pressure and differential are adjustable
externally.
Bellows type devices are available from vacuum to pressures up to
650 psi.

Piston type devices are available for pressures up to 5000 psi.

½

½

½

Piston Type Shown

Optional
SAE 7/16-20 UNF-2B
SAE 9/16-18 UNF-2B

Optional

BS20

Pg 13.5

(27mm)

(69mm)

3/8" - 18 N.P.T.F.

1/8" - 27 N.P.T.F.

Drain

1/2" - 14 N.P.T.

(69mm)

2 23/32"

2 23/32"

17/64"

1 1/16"

(13.5mm)

Dia. Counterbore

17/32"

(6.75mm)

Dia. Mtg. Holes

ATTENTION: Copper alloy bellows may be used on
water or air and other liquids or gases not corrosive to
this alloy. Type 316 stainless steel bellows are available
and are used for the more corrosive liquids and gases.

ATTENTION: Stainless steel piston type controls are
designed for use on oil, water and waterbased fluids but
must not be used on air or gases.

ATTENTION:

The control should not be supported by only

the electricaland pressure connections. A support wrench should
b e u s e d w h e n t i g h t e n i n g t h e e l e c t r i c a l h u b a n d p r e s s u r e
connections.

ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing.

The 2 - Circuit contact block has one set of normally open and one set
of normally closed contacts. These contacts may be arranged for
single pole double-throw operation or separate circuit operation having
the same polarity.
A 4 - Circuit contact block assembly with two normally open and two
normally closed contacts is also available. An isolated terminal is
furnished to provide a termination point when an optional power
source is used. These contacts may be arranged for double pole
double-throw operation or two isolated single pole double-throw,
electrically isolated circuits. Circuits must be of the same polarity.

MOUNTING - The pressure control should be mounted securely to a
firm base using two mounting screws. The recommended fastener for
mounting is a 1/4"-20 or M6X1 metric screw. The applied torque
should not exceed 70 lb-in (8 Nm).The mounting holes (see sketch)
are easily accessible without removing the front cover assembly.