Warnings – Lenze E82MV752 4Bxxx Manuel d'utilisation

Page 3

Advertising
background image

3

EDK82MV752-BB DE/EN/FR 1.0

Warnings!

ƒ

Motor Overload Protection

For information on the protection level of the internal overload

protection for a motor load, see the corresponding manuals or

software helps.

If the integral solid state motor overload protection is not used,

external or remote overload protection must be provided.

ƒ

Branch Circuit Protection

The integral solid state protection does not provide branch circuit

protection.

Branch circuit protection has to be provided externally in accordance

with corresponding instructions, the National Electrical Code and any

additional codes.

ƒ

If mounted on a motor the environmental rating tests for Type 4 and

Type 12 shall be performed.

ƒ

Fuses/circuit breakers

See this manual for maximum fuse/circuit breaker sizes and circuit

breaker types.

Voltage rating of the fuses and circuit breakers must at least be

suitable for the input voltage.

ƒ

E82MV251_2B ... E82MV371_2B (0.25 kW ... 0.37 kW, 240 V devices):

Suitable for use on a circuit capable of delivering not more than

5000 rms symmetrical amperes, 240 V maximum, when protected by

fuses or circuit breakers.

Suitable for use on a circuit capable of delivering not more than

50000 rms symmetrical amperes, 240 V maximum, when protected by

CC, J, T or R class fuses.

Maximum surrounding air temperature: 0 ... +60 °C

> +40 °C: reduce the rated output current by 2.5 %/°C

Use 60/75 °C or 75 °C copper wire only.

ƒ

E82MV551_4B ... E82MV752_4B (0.55 kW ... 7.5 kW, 400/500 V devices):

Suitable for use on a circuit capable of delivering not more than

5000 rms symmetrical amperes, 500 V maximum, when protected by

fuses or circuit breakers.

Circuit breakers only for use in WYE 480/277V source.

Suitable for use on a circuit capable of delivering not more than

50000 rms symmetrical amperes, 500 V maximum, when protected by

CC, J, T or R class fuses.

Maximum surrounding air temperature: 0 ... +60 °C

> +40 °C: reduce the rated output current by 2.5 %/°C

Use 60/75 °C or 75 °C copper wire only.