6

Cold weather installations

An additional back draft damper should be installed to minimize
backward cold air flow and a thermal break should be installed to
minimize conduction of outside temperatures as part of the vent
system. The damper should be on the cold air side of the thermal
break.

The break should be as close as possible to where the vent
system enters the heated portion of the house.

Makeup air

Local building codes may require the use of makeup air systems
when using ventilation systems with greater than specified CFM
of air movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.

Venting Methods

This range hood is factory set for venting through the roof or
through the wall.

The vent system needed for installation is not included.
A 6" (15.2 cm) round vent system is recommended.

Calculate Vent System Length

The recommended vent system is 6" (15.2 cm) round vent with a
maximum length of 35 ft (10.7 m). For the best performance, use
no more than three 90° elbows.

To calculate the length of the system, add the equivalent feet
(meters) for each of the vent pieces used in the system.

Example vent system - 6" (15.2 cm)

Non-Vented (recirculating) Installations Through the
Soffit/Cabinet

If it is not possible to vent cooking fumes and vapors to the
outside, the range hood can be used in the non-vented
(recirculating) version, using a charcoal filter. Charcoal Filter Kit
Part Number W10272068 is available from the dealer or an
authorized parts distributor.

NOTE: 12" (30.5 cm) high cabinets without a soffit may allow the
6" (15.2 cm) vent and vent cover to be seen.

Roof Venting

Wall Venting

A. 6" (15.2 cm) vent through

the roof

B. Roof cap

A. 6" (15.2 cm) vent through

the wall

B. Wall cap

Vent Piece

6" (15.2 cm)

45° elbow

2.5 ft
(0.8 m)

90° elbow

5.0 ft
(1.5 m)

A

B

A

B

Maximum Length

= 35 ft (10.7 m)

1 - 90° elbow

= 5 ft (1.5 m)

1 - wall cap

= 0 ft (0 m)

9 ft (2.8 m) straight

= 9 ft (2.8 m)

System length

= 14 ft (4.3 m)

Through Cabinet

Through Soffit

A. Ceiling
B. Vent cover

C. Soffit
D. 6" (15.2 cm) vent

E. Range hood

F. Cabinet

G. Wall

H. 12" (30.5 cm) min. cabinet

height

I. 17" (43.2 cm) min. vent cover

height

90˚ elbow

3 ft

(0.93 m)

6 ft (1.8 m)

Wall cap

A

A

B

B

C

D

D

E

E

F

F

G

G

I

H