3.7 TOP EXIT HORIZONTAL TERMINATION

16.5A

Simple venting confi guration (only one 45° and 90°
elbow)

(H

T

) < (V

T

)

For vent confi gurations requiring more than one 45° elbow and 90° elbow, the following formulas
apply:

Formula 1: H

T

< V

T

Formula 2: H

T

+ V

T

< 40 feet (12.2m)

Example:

V

1

= 8 FT (2.4m)

V

T

= V

1

= 8 FT (2.4m)

H

1

= 2.5 FT (0.8m)

H

2

= 2 FT (0.6m)

H

R

= H

1

+ H

2

= 2.5 FT (0.8m) + 2 FT (0.6m) = 4.5 FT (1.4m)

H

O

= .03 (one 45° elbow + two 90° elbows - 135°) = .03 (225 - 135°) = 2.7 FT (0.8m)

H

T

= H

R

+ H

O

= 4.5 FT (1.4m) + 2.7 FT (0.8m) = 7.2 FT (2.2m)

H

T

+ V

T

= 7.2 FT (2.2m) + 8 FT (2.4m) = 15.2 FT (4.6m)

Formula 1:

H

T

< V

T

7.2 FT (2.2m) < 8 FT (2.4m)

Formula 2:

H

T

+ V

T

< 40 FT (12.2m)

15.2 FT (4.6m) < 40 FT (12.2m)

Since both formulas are met, this vent confi guration is acceptable.

90°

90°

45°

V

1

H

1

H

2

0

2.5

(0.8)

5

(1.5)

7.5

(2.3)

10

(3.1)

12.5

(3.8)

15

(4.6)

40 (12.2)

10 (3.1)

20 (6.1)

30 (9.1)

17.5

(5.3)

20

(6.1)

39 (11.9)

REQUIRED

VERTICAL

RISE IN FEET

(METERS) V

T

HORIZONTAL VENT RUN PLUS OFFSET IN

FEET (METERS) H

T

See graph to determine the required vertical

rise V

T

for the required horizontal run H

T

.

The shaded area within the lines represents

acceptable values for H

T

and V

T