TroubleshooTing

SCC-30AB is very rugged and designed for the most extreme operating conditions.
Most PV system problems will be caused by connections,Voltage drops, and loads.
Troubleshooting the SCC-30AB controller is simple. Some basic troubleshooting
procedures are listed below.

Protections & Fault Messages on the LCD Display & Fault LED

Table 7.1 gives fault messages displayed on the LCD screen and status of the Red Fault
LED when SCC-30AB stops operating due to protections / system error:

DISPLAy

FAULT
LED

DESCRIPTION

CAUSE OF FAULT / REMEDy

Alarm: OC
Over Current

Solid
Red

Over
Current

Input current exceeds 45A

Alarm: OT

Blinking
Red

Heat Sink over
Temperature

Heat sink temperature exceeds 90ºC

Alarm: CPF00
Link Master
Error

Solid
Red

Display Panel
Error

The CPU is not able to exchange data with
the Display Panel

Alarm: CPF04
DC / DC
LowV

Solid
Red

Low
Voltage

3. Low Battery Voltage:

< 9V for 12V Battery
< 18V for 24V Battery

4. If this symptom is for a 12V Battery

System, check & ensure that DIP Switch
1 at the back of the unit is selected for
12V battery and not for 24V battery.

Alarm: CPF09
Heat Sink SR
Open

Solid
Red

Low Operating
Temperature

Operating temperature is below 0ºC (32ºF).
Ensure operating temperature is above 0ºC
(32ºF).

Battery
Temperature
Sensor (BTS)
displays
- - - ºC

N/A

Battery
Temperature
is below 0ºC

1. Lower limit of temperature compensation

is 0ºC.

2. Negative values can’t be displayed.

Table 7.1. Fault Indications & Remedies