QUICK START GUIDE

RAM 9000 Series

LTE, HSPA & EVDO

VERIFY CELLULAR CONNECTIVITY

Confirm the following on the GUI (see Figure B) after logging into
the unit:
Activation:

“Succeeded” or “Unavailable”

Connection:

“Enabled”

IP Address: Populated with a network IP address

Signal Strength has GREEN bars populated. If you see any RED
bars represented under the Signal Strength graphics, please
consult the User Manual. Ethernet (Eth0) should show “Up” and
show the network issued IP address.

NOTE:

If “Unavailable” and connection “Unknown” browse to the

StatusEZ Config Wizard or Network Tab Cellular

Connection Configuration and input the APN field. EVDO

models will automatically try to activate on a periodic basis.

If you were unable to confirm this status on the Main page, please
refer to the RAM 9000 Software Guide for troubleshooting steps
at

www.sixnet.com

.

For more information to set up Modbus features, please refer to
the RAM 9000 User Guide available at

www.sixnet.com

.

If you are able to confirm this status, then your unit is
successfully connected to the cellular network.

RED LION WIRELESS TECHNICAL SUPPORT

If you have followed all of the instructions up to this point, have
verified with your carrier that you are not having an authentication

problem, have verified that you have adequate cellular signal
reception, and your unit is still not communicating, then it is time to
contact Red Lion Wireless Technical Support at
[email protected] or 1-877-432-9908 and we will be happy to
assist you in getting your unit operational.

HARDWARE STATUS LEDs

LED

State

Description

P1/P2

ON

Power is applied to the associated input

OFF

Power is not being applied to the associated input

GPS

ON

Position fix available

OFF

No position fix available

RESET

ON

Unit is booting. Not Ready

OFF

Unit is functioning normally

WAN

ON

Cellular connection is established

OFF

Cellular Connection is not established

STATUS

ON

Unit is booting up.

OFF

Normal operation

FLASH

Unit entering reflashing mode. Do not disturb.

STROBE

System erros Contact Red Lion support.


*See the RAM 9000 Series Hardware & Installation Guide for more
information on LEDs.




INSTALLATION AND HAZARDOUS AREA WARNINGS


All power, input and output (I/O) wiring must be in accordance with Class
I, Division 2 wiring methods and in accordance with the authority having
jurisdiction.

Suitable for use in Class I, Division 2, Groups A, B, C and D hazardous
locations, or non-hazardous locations only.

WARNING

– EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS

MAY IMPAIR SUITABILITY FOR CLASS 1, DIVISION 2.
WARNING

– EXPLOSION HAZARD – WHEN IN HAZARDOUS

LOCATIONS, DISCONNECT POWER BEFORE REPLACING OR WIRING
MODULES.
WARNING

– EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT

UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN
TO BE NONHAZARDOUS.
WARNING

– EXPLOSION HAZARD BATTERIES MUST ONLY BE

CHANGED IN AN AREA KNOWN TO BE NON-HAZARDOUS.


These products are operator interface units to be used within control
panels. These devices are intended for use in Class I, Division 2,
Hazardous Locations, industrial control applications. The enclosure shall
be suitable for the location.

A minimum IP54 rated enclosure is needed for ATEX unless an
equivalent degree of protection is supplied by the location.
These products are to be used within control panels in hazardous
locations. The enclosure shall be suitable for this location. Hot-swapping
is not for use in hazardous locations.

AVERTISSEMENTS POUR INSTALLATION ET ENDROITS
DANGEREUX


Tout courant, câblage entrée et sortie (I / O) doit être conforme aux
méthodes de câblage à la Classe I, Division 2 et conformément à
l'autorité compétente.

Cet appareil est adapté pour utilisation en Classe I, Division 2, Groupes
A, B, C, D endroits dangereux ou endroits non-dangereux.

AVERTISSEMENT

– RISQUE D’EXPLOSION – LA SUBSTITUTION DE

TOUT COMPOSANT PEUT NUIRE À LA CONFORMITÉ DE CLASSE I,
DIVISION 2
AVERTISSEMENT

– RISQUE D’EXPLOSION – LORSQUE DANS DES

ENDROITS DANGEREUX, DÉBRANCHEZ LE CORDON D'ALIMENTATION
AVANT DE REMPLACER OU DE BRANCHER LES MODULES.
AVERTISSEMENT

– RISQUE D’EXPLOSION – NE DÉBRANCHEZ PAS

L'ÉQUIPEMENT À MOINS QUE L'ALIMENTATION AIT ÉTÉ COUPÉE OU
QUE L’ENVIRONNEMENT EST CONNU POUR ÊTRE NON DANGEREUX.
WARNING

– RISQUE D’EXPLOSION - LES BATTERIES DOIVENT ÊTRE

REMPLACÉES DANS UNE ZONE CONNUE COMME ÉTANT NON-
DANGEREUSE.


Ces produits sont des unités d'interface opérateur qui doivent être
utilisés à l'intérieur des panneaux de commande. Ces appareils sont
destinés à une utilisation en Classe I, Division 2, zones dangereuses,
applications de contrôle industriel. L'enclos doit être adapté à
l’environnement lieu.

Un boîtier IP54 minimum est nécessaire pour ATEX à moins qu’un degré
équivalent de protection est fourni par l'emplacement.
Lorsque dans des endroits dangereux, ces produits doivent être utilisés
dans des panneaux de contrôle. Pas de remplacement à chaud des
modules dans les zones dangereuses.