Red Lion RA 9000 Cellular RTU Manuel d'utilisation

Quick start guide ram 9000 series

Advertising
background image

Red Lion Controls

• 20 Willow Springs Circle • York, PA 17406 • USA • +1 717 767 6511

www.redlion.net

QUICK START GUIDE

RAM 9000 Series

LTE, HSPA & EVDO

UNPACKING INSTRUCTIONS

1

Unpack the Red Lion unit and verify the following
components are enclosed for the

RAM 9xxx RTU

:

Unit and Quick Start Guide.

Power Supply, Antennas and accessories sold
separately.


2

Contact your cellular provider (carrier) and request a data
account. For EVDO models (

RAM

96xx), give the ESN

number of the router to the carrier to activate the data
account. For LTE models (

RAM

97xx) the carrier should

provide you with a SIM card to insert into the router, along
with the APN, username, & password for data connectivity.

3

Insert the SIM card (LTE models only):

Locate the SIM Card(s) & Battery panel on the bottom
of the RTU. Open panel by removing single screw.

Insert the card as shown on the silkscreen next to the
slot.

Push the SIM card in until it clicks. Close panel and
secure with a single screw.

4

An antenna with an SMA-M connector should be connected
to the RTU directly or via a coaxial cable. This antenna
should meet the specifications listed below. Also see the
Hardware & Installation Guide for more information on
antennas.

3G: Dual-band 800 & 1900 MHz

LTE: 700 MHz

Nominal 50 ohm impedance

Voltage Standing Wave Ratio (VSWR) less than 2.5:1

5

Power is supplied to the RTU via the 6-screw plug on the

top. Device accepts 8-30 VDC power. (Power supply /
transformer not included)

Power connector

(top of unit)

Pin

Name

Description

P1+

Power 1+

This is the primary power

source input(+)

P1-

Power 1-

This is the primary power

source input(-)

Chassis

Ground

Tie to the panel or chassis

ground.

P2+

Power 2+

This is the secondary (backup)

power source input(+)

P2-

Power 2-

This is the secondary (backup)

power source input(-)

Chassis

Ground

Tie to the panel or chassis

ground.

6

Please allow 1-2 minutes for the unit to recognize the
cellular unit and connect to the cellular network. When this
has occurred the Signal Strength LEDs should light up (see
table on back). If signal strength is not lit or flashes slowly,
please refer to the User Manual at

www.sixnet.com

.

7

Connect to the Ethernet RJ45 port for network connectivity.

ACCESSSING THE GRAPHICAL USER INTERFACE (GUI)

1

Connect PC to the RAM 9000 Unit

Connect an Ethernet cable or a USB Cable between the
local PC and the unit’s Ethernet 0 port (E0). Verify the link
LED is lit.

2

Setup PC IP Address

For assistance with configuring your PC, see the appropriate
Microsoft Windows support webpage listed at:

http://support.microsoft.com

.

PC to Ethernet Interfaces
Select “Use the following IP address” and fill in the blank
fields with the information below:

Ethernet 0

IP address

192.168.0.2

Subnet mask

255.255.255.0

Default gateway

192.168.0.1

Preferred DNS

192.168.0.1

3

Access Graphical User Interface

Open a web browser and enter the following in the
address bar:

http://192.168.0.1:10000/

LOGIN INSTRUCTIONS

• User Name enter:

admin (lowercase letters)

• For Password enter:

last six digits of the unit serial number (lowercase)


Upon successfully logging in you will see the following screen

:

You are now connected to the Management GUI. If you
should see anything other than the GUI screen shown,
please refer to the Red Lion RAM 9000 Series User
Manual located at:

www.sixnet.com

.


Advertising