Figure 4. surface housing, 2 transfer points – Edwards Signaling 1508 Manuel d'utilisation

Page 2

Advertising
background image

5.

Mount the connected assembly onto the surface housing

and secure it with (2) #10-32 x 7/8" screws (supplied).

NOTE: The combined projection of the surface housing,

electromagnet assembly, and the armature assembly

is 4 1/16".

Armature Assembly Mounting

NOTE: Armature assembly must be mounted vertically

(Figure 3) to obtain correct alignment with the

electromagnet.

1.

Using a 5/32" Allen wrench, turn the contact plate adjusting

screw (Figures 5 and 6) counterclockwise to loosen the

contact plate.

2.

Place the transfer marking points in the armature mounting

holes (Figure 3).

3.

To locate the two mounting holes in the door, hold the contact

plate centered against the magnet, open the door and press

against the transfer marking points on the armature base.

Release the door and remove the transfer marking Points.

4.

Mount the armature assembly using one of the following

methods:

a.

Thru-bolt mounting (Figure 5). Center punch the two

holes (at the points marked in step 3) and drill 5/16"

diameter through the door. Distance between the center

points should equal 1 3/4".

NOTE: Thru-bolt mounting is recommended for standard

1 3/4" hollow metal, hollow core or composite type

wood doors.

120V AC 24V AC/

DC

COM

FRONT

VIEW

TOP

VIEW

Figure 2. Terminal Block

Figure 5. Thru-Bolt Mounting

Figure 6. Surface Concealed Mounting

Secure the armature assembly, with the contact plate

adjust screw facing down, to the door as shown in

Figure 5 using (2) #1/4-20 x 2" screws (supplied)

NOTE: For 2" doors, use (2) 1/4-20 x 2-1/4" bolts.

b. Surface concealed mounting (Figure 6). Measure two

points for 1/8" holes drilled 1/2" on center equidistant

from each marked point. Center punch the holes and

drill 1/8" diameter x 1 1/4" deep. Install the concealed

mounting plate using the two #10 x 1 1/2" screws

provided.

NOTE: Surface concealed mounting is not recommended for

hollow metal, hollow core, or composite type wood

doors.

Align the holes for the concealed mounting plate in the

armature base with the pins on the concealed mounting

plat. Secure the armature assembly, with the contact

plate adjust screw facing down, to the door by tightening

the set screw as shown in Figure 6.

5.

Align the contact plate against the electromagnet. The

contact plate must be centered and lie flat against the magnet

to ensure sufficient holding force. Tighten the contact plate

adjusting screw until the plate is firm but not set. Do not

overtighten the contact plate.

6.

Recheck alignment and adjust if necessary.

7.

Adjust the door closer to exert 3 pounds of force when the

door is open and armature and magnet are in contact.

8.

Check operation.

NOTE: The unit will not operate without electrical power.

Figure 3. Mounting the Armature Assembly

P/N 3100538 ISSUE 1
501-152700-0-01

PAGE 2

Mounting holes

Armature

(base view)

Figure 4. Surface Housing

2 Holes for

mounting housing to wall

2 Holes for mounting

magnet assembly to housing

Ground wire connection

Field wiring entrance hole

GND

1 Hole for securing field
wiring protector

Acrylic Insulating Sleeve

1 3/4"

Door Plate

1 5/8"

DOOR

(2) #1/4-20 x 2"

screws provided

for a standard

1 3/4"

door

2" from floor to center

Contact plate

adjusting screw

Mounting holes

Armature

(base view)

2 Transfer points

Holes for
concealed
mounting
plate

Armature

(base view)

Top of

door

Lock edge
of door

2 3/8"

(60 mm)

2 5/8" (67 mm)

approx.

5" (127 mm)

approx.

1 11/16"
(43 mm)

Concealed
mounting
plate

1/2"

Two #10 x 1 1/2"

screws (supplied)

Set screw.
Tighten with 6/32" Allen wrench
to secure armature onto
mounting plate.

Door

Contact plate

Contact plate
adjusting screw

1/2"

Advertising