Installation Instructions for Surface Wall Mount Electromagnetic Door

Holders Catalog Series 1508

P/N 3100538 ISSUE 1 © 2003

501-152700-0-01

Description

The 1508 Series are surface wall mount door holders for use with

single doors. All are UL and cUL Listed and FM approved.

Installation

Install and wire in accordance with applicable codes, standards,

such as NFPA publications 70 (National Electrical Code), 72 (Na-

tional Fire Alarm Code), and 80 (Standard for Fire Doors and Fire

Windows), and/or other regulations applicable to the country

and locality of installation and in accordance with authorities

having jurisdiction.

Table 1. Specifications

Cat. No.

Volts

Amps

1508-E1

12V DC

0.170

1508-E5

12V AC 60 Hz

0.150

1508-AQN5

24V AC 60 Hz

0.015

24V DC

0.015

120V AC 60 Hz

0.015

1.

Using Figure 1 and Table 2, locate the intersection of

Dimension X and Dimension Y. Dimension Z is shown at the

intersection in the gray area.

NOTE: If dimension X or Y is not shown on the chart,

extrapolate Dimension Z. (i.e., if X=7, and Y=30, Z

= (27-5/8 - ((27-5/8 - 27-1/4)/2)) => Z = 27-9/16" )

2.

Mount the surface housing (supplied) vertically on the

horizontal center line and 5" from the top of the door with

two 1/4-20 x 1" screws (provided).

NOTE: The outlet box must be able to withstand a maximum

holding force of 50 pounds.

If X and Y intersect in the blank area in Table 2, DO NOT

install the outlet box. The contact plate and electromagnet

cannot be aligned with these dimensions.

Door

Door jamb

Wall line

Outlet box

center

line

X

Z

Y

Figure 1. Locating the Door Holder

Table 2. Dimension chart (in inches (mm))

Electromagnet Assembly Mounting

1.

Refer to Figure 4. If not using surface metal raceway (not

supplied), secure the acrylic insulating sleeve (provided) to

the hole in the surface housing with the #8-32 x 3/16" screw

provided.

WARNING

To prevent electrical shock, ensure power is discon-
nected.

2.

Pull field wiring through conduit into the surface housing. If

surface metal raceway (not supplied) is being used, the

required size is 1/2" wide x 11/32" high. The raceway will

seat 1/4" into the surface housing. Wiring should be run

through the acrylic insulating sleeve where applicable.

3.

Establish earth-ground continuity in accordance with

applicable codes, standards and authorities having

jurisdiction.

4.

For -E1 and -E5 models, connect the field power wiring to the

electromagnet assembly wiring leads.

For -AQN5 models, refer to Figure 2 and connect as

instructed below:

a.

120V AC operation. Connect power field wiring to

terminals marked "120V AC" and "COM."

b. 24V AC/DC operation. Connect power field wiring to

terminals marked "24V AC/DC" and "COM."

CHESHIRE, CT 203-699-3300

CUST. SERV. FAX

203-699-3365

TECH SERV. FAX

203-699-3078

28

30

32

34

36

38

40

42

44

46

48

2 26 (660)

28 (711)

29 7/8 (759)

32 (813)

34 (864)

36 (914)

38 (965)

40 (1016)

42 (1067)

43 7/8 (1114) 45 5/8 (1159)

4 26 (660)

28 (711)

29 7/8 (759)

32 (813)

34 (864)

36 (914)

38 (965)

40 (1016)

42 (1067)

43 7/8 (1114) 45 5/8 (1159)

6 25 5/8 (651)

27 5/8 (702)

29 5/8 (752)

31 3/4 (806)

33 3/4 (857)

35 3/4 (908)

37 3/4 (959)

39 3/4 (1010) 41 3/4 (1060) 43 5/8 (1108) 45 3/8 (1153)

8 25 1/4 (641)

27 1/4 (692)

29 1/4 (743)

31 3/8 (797)

33 1/2 (851)

35 1/2 (902)

37 3/8 (949)

39 1/2 (1003) 41 1/2 (1054) 43 3/8 (1102) 45 1/4 (1149)

10 24 5/8 (625)

26 3/4 (679)

28 3/4 (730)

30 7/8 (784)

33 (838)

35 (889)

37 (940)

39 1/8 (994)

41 1/8 (1045) 43 (1092)

44 7/8 (1140)

12 23 3/4 (603)

25 7/8 (657)

28 (711)

30 1/8 (765)

32 1/4 (819)

34 3/8 (873)

36 3/8 (924)

38 1/2 (978)

40 5/8 (1032) 42 1/2 (1080) 44 3/8 (1127)

14 23 3/4 (603)

25 (635)

27 1/4 (692)

29 3/8 (746)

31 1/2 (800)

33 3/4 (857)

35 7/8 (911)

38 (965)

40 (1016)

42 (1067)

43 7/8 (1114)

16 21 3/4 (552)

24 (610)

26 1/4 (667)

28 1/2 (724)

30 3/4 (781)

33 (838)

35 1/8 (892)

37 1/4 (946)

39 3/8 (1000) 41 3/8 (1051) 43 3/8 (1102)

18 20 (508)

22 1/2 (572)

25 (635)

27 3/8 (695)

29 3/4 (756)

32 (813)

34 1/4 (870)

36 1/2 (927)

38 5/8 (981)

40 5/8 (1032) 42 1/2 (1080)

20 18 1/4 (463)

21 (533)

23 1/2 (597)

26 (660)

28 1/2 (724)

30 7/8 (784)

33 1/8 (841)

35 3/8 (899)

37 5/8 (956)

39 5/8 (1006) 41 5/8 (1057)

22

18 3/4 (476)

21 5/8 (549)

24 3/8 (619)

27 (686)

29 3/8 (746)

31 3/4 (806)

34 1/8 (867)

36 1/2 (927)

38 5/8 (981)

40 3/4 (1035)

24

22 1/2 (572)

25 1/2 (648)

28 1/8 (714)

30 5/8 (778)

33 1/8 (841)

35 5/8 (905)

37 7/8 (962)

40 (1016)

26 Do not install outlet box if

26 1/4 (667)

29 (737)

31 5/8 (803)

34 1/4 (870)

36 1/2 (927)

38 5/8 (981)

28 Dimensions X and Y intersect in this blank area.

29 3/4 (756)

32 1/2 (826)

34 7/8 (886)

37 1/8 (943)

30 The armature and electromagnet cannot be aligned.

27 3/4 (705)

30 5/8 (778)

33 (838)

35 3/8 (899)

32

31 3/8 (797)

33 7/8 (860)

X =

Di

m

ensi

on of

d

oor

ja

m

b

t

o

wal

l

Y = Dimension of door width

Advertising