Edwards Signaling Genesis WG4 Outdoor Horn Manuel d'utilisation

Genesis wg4 outdoor horn installation sheet, En: installation sheet, Description

Advertising
background image

© 2012 UTC Fire & Security. All rights reserved.

1 / 8

P/N 3101999-ML • REV 1.0 • ISS 11APR12

Genesis WG4 Outdoor Horn Installation Sheet

EN FR

EN: Installation Sheet

Description

The Genesis WG4 Outdoor Horn is a life safety notification
appliance designed for indoor or outdoor use on ceilings or
walls. See Table 1 for a list of models and Table 2 for a list of
accessories.

For surface mount applications, mount the WG4 onto a
Model 449 electrical box using the gasket shipped with the
appliance. For flush mount applications where the mounting
surface is flush with the surface of the wall or ceiling, use the
WG4GSKT gasket kit.

Note that you need a Model 449 electrical box for waterproof
applications, or a standard mount 4 in. square box for all other
applications.

The horn includes field-configurable jumper options that allow
you to set the horn pattern to temporal or continuous, and the
horn volume to low or high.

Table 1: Models

Number Description

WG4WF-H

Outdoor rated wall/ceiling horn, white with FIRE
marking

WG4WN-H

Outdoor rated wall/ceiling horn, white without marking

WG4RF-H

Outdoor rated wall/ceiling horn, red with FIRE marking

WG4RN-H

Outdoor rated wall/ceiling horn, red without marking

Table 2: Accessories

Number Description

WG4WTS [1]

Outdoor-rated surface skirt, white, for Genesis WG4
horn or horn-strobe

WG4RTS [1]

Outdoor-rated surface skirt, red, for Genesis WG4
horn or horn-strobe

WG4GSKT [2] Appliance replacement gasket, flush mount

[1] The trim skirt is outdoor-rated when used with the Model 449
electrical box.
[2] Not compatible with the trim skirts.

To synchronize horn operation, you must install a separate
synchronization source. See Table 3. When connecting the
horn to a listed control panel, verify synchronization operation
on the compatibility list for the corresponding panel.

Table 3: Compatible synchronization source models

Description Number

Auto-sync output
module

SIGA-CC1S SIGA-MCC1S
GSA-CC1S GSA-MCC1S
SIGA-CC2A SIGA-MCC2A

Genesis signal master -
remote mount

ADTG1M-RM

MG1M-RM

EG1M-RM XLSG1M-RM
G1M-RM

ZG1M-RM

Booster or auxiliary
power supply

APS10*

EBPS10*

APS6*

EBPS6*

BPS10*

MIRBPS10*

BPS6*

MIRBPS6*

EAPS10*

XLS-BPS10*

EAPS6*

XLS-BPS

* Represents any number of additional characters

Installation

Install this device in accordance with applicable requirements
and in accordance with the local authorities having jurisdiction.

WARNING:

Electrocution hazard. To avoid personal injury or

death from electrocution, remove all sources of power and
allow stored energy to discharge before installing or removing
equipment.

Notes

Electrical supervision requires that you break the wire run
at each terminal. Do not loop wires around the terminals.

Mount the Genesis WG4 Outdoor Horn horizontally or
vertically on either the wall or ceiling; place the electrical
box accordingly. See Figure 1.

Advertising