2 400-800

Ohms

3

800-1600 Ohms

4 >=1600

Ohms

BURNER (OIL OPERATION)
The electrode spacing must be checked and adjusted, if necessary after every nozzle change. Nozzle should be
replaced annually or sooner if burner cannot be set up to operate properly. Nozzle size and type are marked on the
rating plate.

AFTER INSPECTION, A COMPLETE COMBUSTION TEST MUST BE PEFORMED AFTER EACH ANNUAL

SERVICE OF THE UNIT TO MAINTAIN OPTIMUM PERFORMANCE AND RELIABILITY.

WARNING: TURN OFF THE FUEL SUPPLIES AND POWER BEFORE PERFORMING SERVICE
WORK. THE 120V CIRCUIT IS A POTENTIAL ELECTROCUTION HAZARD.

THE WRAP-AROUND EXCHANGER CAN NOW BE CLEANED ENTIRELY FROM THE CLEAN-OUT PORT AND
THE FLUE PIPE CONNECTION.


HEAT EXCHANGER CLEANING PROCEDURE

1.) REMOVE EASY ACCESS PANEL LOCATED ON TOP HEATER BOX PANEL
2.) REMOVE EASY ACCESS PANEL LOCATED ON TOPSIDE OF HEAT EXCHANGER
3.) SHOVE FLEXIBLE BRUSH VIA ACCESS PANEL AND CLEAN THOROUGHLY
4.) SHOVE FLEXIBLE VACUUM VIA ACCESS PANEL AND VACUUM THOROUGHLY


HEAT EXCHANGER REASSEMBLY AFTER CLEANUP

1.) CLOSE EASY ACCESS PANEL LOCATED ON TOPSIDE OF HEAT EXCHANGER

2.)

CLOSE TOP BOX EASY ACCESS PANEL


COMBUSTION AIR ADJUSTMENTS

Firing rate (GPH)

2

2

2

2

Pump Pressure (PSIG)

100 120 150

200

Input (BTU/h) with NO.1 fuel

277,000

310,240

339,325

391,955

Input (BTU/h) with NO.2 fuel

280,000 313,600 343,000

396,000

BECKETT BURNER