Photoelectric Sensor
6" (15 cm) max. above fl oor

Photoelectric Sensor
6" (15 cm) max. above fl oor

Invisible Light Beam

Protection Area

Sensor Wires

Connect sensor wire to
operator (refer to Wire
Connections, page 6)

INSTALL MODEL CPS-U

MOUNT AND WIRE THE PHOTOELECTRIC
SENSORS

Be sure power to the operator is disconnected.
1. Center each sensor in the bracket with the lenses pointing

toward each other across the door.

2. Attach the sensors to the brackets with the provided hardware.

Finger tighten the receiving sensor wing nut. Securely tighten
the sending sensor wing nut.

3. Run the sensor wires to the operator. Fasten the sensor wire

appropriately.

4 Connect the sensor wires to the operator (refer to Wiring

Connections, page 6).

Sensor Wire

Indicator Light

“C” Wrap

Wing Nut

1/4-20x1-1/2" Hex Bolt

Sensor

ALIGN THE PHOTOELECTRIC SENSORS

1. Connect power to the operator. The green indicator lights in

both the sending and receiving sensors will glow steadily
if wiring connections and alignment are correct.

2. If the receiving sensor indicator light is not glowing steadily

(and the invisible light beam path is not obstructed),
alignment is required:

• Loosen the receiving sensor wing nut to allow slight

rotation of the sensor. Adjust sensor vertically and/or
horizontally until the green indicator light glows steadily.

• When the indicator lights are glowing in both sensors,

tighten the receiving sensor wing nut.

Indicator
Light

6" (15 cm) max. above fl oor

Indicator

Light

6" (15 cm) max. above fl oor

6" (15 cm) max. above fl oor

R

S

S

S

R

R

DOOR #1

DOOR #2

DOOR #3

S

R

R

R

S

S

Recommended installation for adjacent doors and

more than one set of photoelectric sensors.

R = Receiving Sensor

S = Sending Sensor

24" (61 cm) min.