Set receive to transmit delay, Report number of floats, Report receive to transmit delay – VEGA VEGABAR 82 Modbus and Levelmaster protocol - Operating Instructions Manuel d'utilisation

Page 79

Advertising
background image

79

10 Annexe

VEGABAR 82 • Protocole Modbus et Levelmaster

46294-FR-131120

Response:

Paramètres

Length

Code/Data

Set Baud Rate

11 characters ASCII

Exemple : U01B9600E71
Modifier l'appareil à l'adresse 1 en vitesse de transmission 9600, parité paire, 7 bits de données, 1

bit d'arrêt

Set Receive to Transmit Delay

Request:

Paramètres

Length

Code/Data

Set Receive to Transmit Delay

7 characters ASCII

UuuRmmm
mmm = milliseconds (50 up to 250),

default = 127 ms

Response:

Paramètres

Length

Code/Data

Set Receive to Transmit Delay

6 characters ASCII

UuuROK

Report Number of Floats

Request:

Paramètres

Length

Code/Data

Set Receive to Transmit Delay

4 characters ASCII

UuuF

Response:

Paramètres

Length

Code/Data

Set Receive to Transmit Delay

5 characters ASCII

UuuFn
n = number of measurement values

(0, 1 or 2)

Report Receive to Transmit Delay

Request:

Paramètres

Length

Code/Data

Report Receive to Transmit Delay

4 characters ASCII

UuuR

Response:

Paramètres

Length

Code/Data

Report Receive to Transmit Delay

7 characters ASCII

UuuRmmm
mmm = milliseconds (50 up to 250),

default = 127 ms