5 instructions levelmaster, Fc43 sub 14, read device identification – VEGA VEGABAR 82 Modbus and Levelmaster protocol - Operating Instructions Manuel d'utilisation

Page 76

Advertising
background image

76

10 Annexe

VEGABAR 82 • Protocole Modbus et Levelmaster

46294-FR-131120

Request:

Paramètres

Length

Code/Data

Function Code

1 Byte

0x11

Response:

Paramètres

Length

Code/Data

Function Code

1 Byte

0x11

Byte Number

1 Byte

Slave ID

1 Byte

Run Indicator Status

1 Byte

FC43 Sub 14, Read Device Identification

Ce code de fonction permet d'interroger l'identification du dispositif (Device Identification).
Request:

Paramètres

Length

Code/Data

Function Code

1 Byte

0x2B

MEI Type

1 Byte

0x0E

Read Device ID Code

1 Byte

0x01 to 0x04

Object ID

1 Byte

0x00 to 0xFF

Response:

Paramètres

Length

Code/Data

Function Code

1 Byte

0x2B

MEI Type

1 Byte

0x0E

Read Device ID Code

1 Byte

0x01 to 0x04

Confirmity Level

1 Byte

0x01, 0x02, 0x03, 0x81, 0x82, 0x83

More follows

1 Byte

00/FF

Next Object ID

1 Byte

Object ID number

Number of Objects

1 Byte

List of Object ID

1 Byte

List of Object length

1 Byte

List of Object value

1 Byte

Depending on the Object ID

10.5 Instructions Levelmaster

Le VEGABAR 82 est aussi approprié au raccordement aux RTU suivants avec protocole Levelmas-

ter. Le protocole Levelmaster est très souvent appelé "protocole Siemens" ou "protocole cuve".

RTU

Protocol

ABB Totalflow

Levelmaster

Kimray DACC 2000/3000

Levelmaster

Advertising