Installation – FERROLI FG Manuel d'utilisation

Page 8

Advertising
background image

FG

8

GB

cod. 3540I950 - 06/2007 (Rev. 00)

2. Installation

2.1 General Instructions

BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH
ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRE-
SCRIPTIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER WORKMANSHIP.

2.2 Place of installation

The boiler must be installed in a special room with ventilation openings towards the outside in conformity with current
regulations. If there are several burners or extractors that can work together in the same room, the ventilation openings
must be sized for simultaneous operation of all the units. The place of installation must be free of flammable objects or
materials, corrosive gases, volatile substances or dusts that can be sucked by the fan. The room must be dry and not
exposed to rain, snow or frost.

A

Ensure enough space around the unit for removing the casing and for normal servicing operations. In partic-
ular, make sure there is enough space in the front part of the boiler for loading the fuel.

2.3 Plumbing connections

The heating capacity of the unit must be previously established by calculating the building's heat requirement according
to current regulations. The system must be provided with all the components for correct and regular operation. It is ad-
visable to install on-off valves between the boiler and heating system allowing the boiler to be isolated from the system
if necessary.

B

The safety valve outlet must be connected to a funnel or collection pipe to prevent water spurting onto the floor
in case of overpressure in the heating circuit. Otherwise, if the drain valve is activated and floods the room,
the boiler manufacturer cannot be held liable.

Do not use the water system pipes to earth electrical appliances.

Before installation, carefully wash all the pipes of the system to remove residuals or impurities that could affect correct
operation of the unit.

Carry out the relevant connections according to the diagram in cap. 4 "Technical data and characteristics" and the sym-
bols given on the unit.

Characteristics of the water system

In the presence of water harder than 25° Fr (1°F = 10ppm CaCO3), use suitably treated water in order to avoid possible
scaling in the boiler. Treatment must not reduce the hardness to values below 15°F (Decree 236/88 for uses of water
intended for human consumption). Treatment of the water used is indispensable in case of very large systems or with
frequent introduction of replenishing water in the system.

Antifreeze system, antifreeze fluids, additives and inhibitors

If necessary, antifreeze fluids, additives and inhibitors can be used only if the manufacturer of these products guaran-
tees that they are suitable for this use and do not cause damage to the boiler exchanger or other components and/or
materials of the unit and system. Do not use antifreeze fluids, additives or inhibitors that are not specific for use in heat-
ing systems and not compatible with the boiler materials and system.