Warning, Installation and wiring cont, Testing – White Rodgers 668 Manuel d'utilisation

Page 2

Advertising
background image

2

Possible Cause of

Correction

Trouble

Open circuit in Cell

Replace Cell (or Cell Assembly)
of 956 Flame Detector. Do not
disturb position of bracket or
socket assembly.

Flame detector

Locate flame detector according

improperly positioned.

to the burner manufacturer’s
specifications.

The following control checks should be made after each
installation to insure that the controls are correctly wired
and functioning properly.
1.

Open the main line switch.

2.

Adjust thermostat or operating control to call for heat.

3.

Operate the manual reset button on top of control.

4.

Make certain that high limit control is set at the correct
temperature.

5.

Open the hand valve in the oil line. The system is now
ready for the following tests.

A. NORMAL CYCLE:

Close the line switch. The burner should start and
continue to run normally. (If burner starts, establish-
ing flame, but then locks out on safety, make “Flame
Detector Check” at this time.

B. SAFETY TIMING:
1.

Let the burner run for about 5 minutes. Then remove
one of Flame Detector leads from the “F” terminals.
After a time period corresponding to the safety timing
has elapsed, the control should lock out on safety,
stopping the burner.

2.

Open the line switch.

3.

Replace Flame Detector lead removed in step 1.

4.

Wait about 3 minutes. Then operate the manual reset
button on top of control.

C. HIGH LIMIT AND THERMOSTAT CHECK:
1.

Close the line switch to start the burner.

2.

Lower the setting of the high limit control to its lowest
setting. This should stop the burner, unless furnace or
boiler temperature is below the minimum setting of the
high limit.

3.

Return high limit control to its proper setting. Burner
should restart.

4.

With the burner running, turn thermostat to its lowest
setting. This should stop the burner, unless actual
room temperature is below the lowest setting of the
thermostat.

On systems supplying domestic hot water, burner
will continue to run if low limit control is not
satisfied.

INSTALLATION AND WIRING CONT.

All wiring should be done in accordance with local and national electrical codes and ordinances.

LOW VOLTAGE PRIMARY CONTROL

LINE VOLTAGE PRIMARY CONTROL

External Line Voltage Wiring

External Line Voltage Wiring

TESTING

5.

Return thermostat to its proper setting.

D. FLAME DETECTOR CHECK: (This test is not re-

quired if the control performs as described in test
A.)

If the burner starts but the control locks out (stopping the
burner), check the flame detector as follows:
1.

Open the line switch.

2.

Connect one end of a wire jumper to one of the “F”
terminals.

3.

Start the burner by closing the line switch. As soon as
the flame has been established, connect the other end
of the wire jumper to the other “F” terminal.

The control provides no safety protection with
this jumper installed. Do NOT leave burner in this
condition except for making this check.

If the control still locks out with the jumper installed, the
control should be replaced. If the control does not lock out,
however, check the operation of the 956 flame detector as
follows:

T

T

F

F

ORANGE

WIRE
NUTS

THERMOSTAT

FLAME

DETECTOR

FLAME

DETECTOR

FIELD

INSTALLED

JUMPER

LINE VOLTAGE

THERMOSTAT OR

OPERATING

CONTROL

IGN.
TRANS.

WIRE
NUTS

IGN.
TRANS.

PRIMARY
CONTROL

WHITE

BLACK

LIMIT

LINE

HOT

N

BURNER

MOTOR

ORANGE

PRIMARY
CONTROL

WHITE

BLACK

LIMIT

LINE

HOT

N

BURNER

MOTOR

T

T

F

F

NOTE

WARNING

!

CELL ASSEMBLY

SOCKET

ASSEMBLY

CELL

BRACKET

OLD STYLE

NEW STYLE

Rotate Cell Assembly coun-
terclockwise to remove it.
To replace it insert end
through notched opening in
bracket and rotate clock-
wise. NOTE: If bracket is
ever removed from burner,
Cell Assembly will not fit if
bracket is reinstalled back-
wards.

TYPE 956 FLAME DETECTORS