INSTALLATION

WHEN

INSTALLED WITH BLOWER

KIT EP63

For reduced clearances installation must comply with

NFPA 211or CAN/CSA-B365.

Alcove installation

Model 1600C-1 may be installed into an alcove having a

depth of not more than 4 feet and a height of at least 7 feet,

when using a listed double wall connector that is rated for a

minimum 12” clearance to combustible material.

The minimum clearances are as shown.

Stove installation

If the stove is to be installed on a

combustible floor, it must be

placed

on

a

approved

non-combustible hearth pad,

that extends 8" (200mm)

beyond the stove sides and

back, and 18" (455mm) to the

front.

Listed single wall chimney connector

Flue configuration

Type 1

Horizontal

Vertical

FROM

UNIT

A

16”

16”

B*

10”

16”

C

11”

11”

FROM

PIPE

D

25”

25”

E

...

18”

F

...

18”

* A 18 in. Minimum clearance should be maintained

from combustible wall to the chimney connector.

Double walled connectors listed for a minimum

clearance of 12” or less from combustible materials

must be used to achieve the following clearances.

Flue configuration

Type 2

Horizontal

Vertical

FROM

UNIT

A

16”

16”

B

10”

10”

C

11”

11”

FROM

PIPE

D

25”

25”

E

...

16”

F

...

12”

6

1 6 "

1 6 "

1 6 "

4 f o o t m a x

8 "

1 8 "

8 "

8 "

A

B

F

D

E

C

C

8 4 "

I l l u s t r a t e d w i t h . 7 5 " h e a r t h p a d .

Alcove installation

Walls shall not extend from front of unit when installed

in the alcove configuration.