Obsolete, Installer setup – Honeywell FOCUSPRO TH5110D Manuel d'utilisation

Page 6

Advertising
background image

Installation Guide



To begin, press and hold the

s

and FAN

buttons until the display changes.

Function

number

Setting

Press

s

or

t

to change settings.

Press NEXT to advance to the next function.

Press DONE to exit and save settings.

1

0

Done

Next

Installer setup

Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.

Continued on next page

Setup function

Settings & options (factory default in bold)

Shaded areas below apply only to

TH5220D

.

*[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]

1

System type

0

1 heat/1 cool conventional

1

1 heat/1 cool heat pump (no aux. heat)

2

Heat only — 2-wire systems, 3-wire zone valves (Series 20), and

normally open zone valves

3

Heat only with fan

4

Cool only

5

2 heat/1 cool heat pump (with aux. heat)

6

2 heat/2 cool conventional

7

2 heat/1 cool conventional

8

1 heat/2 cool conventional

2

Changeover valve

(O/B terminal)

0

Changeover valve (O/B terminal energized in cooling)

1

Changeover valve (O/B terminal energized in heating)

3

Fan control

(heating)

0

Gas or oil furnace — equipment controls fan in heating

1

Electric furnace — thermostat controls fan in heating

5

Stage 1 heat cycle

rate (CPH: cycles/hour)*

5

For gas or oil furnaces of less than 90% efficiency

1

For steam or gravity systems

3

For hot water systems & furnaces of over 90% efficiency

9

For electric furnaces

6

Stage 2 heat cycle

rate/Auxiliary heat

cycle rate (CPH)*

5

For gas or oil furnaces of less than 90% efficiency

1

For steam or gravity systems

3

For hot water systems & furnaces of over 90% efficiency

9

For electric furnaces

8

Emergency heat cycle

rate (CPH)*

9

For electric emergency heat

1

For steam or gravity systems

3

For hot water systems & furnaces of over 90% efficiency

5

For gas or oil furnaces of less than 90% efficiency

OBSOLETE