Wiring diagram, Electronic expansion valve (eev), Fault codes – Bradford White RE2H50R10 Manuel d'utilisation

Page 2: L1 l2

Advertising
background image

Electronic Expansion Valve (EEV)

This valve replaces the capillary tube typically used in

refrigeration appliances. The EEV meters the flow of liquid

refrigerant entering the evaporator at the rate that matches

the amount of refrigerant being boiled off in the evaporator

(gas). the valve also maintains the proper “superheat”

(T3b-T3a).

Superheat is the temperature of a gas above the boiling point

for the liquid. If a refrigerant liquid boils at a temperature of

40ºF in a cooling coil, and then the refrigerant gas increases

in temperature, superheat has been added. If this refrigerant

changed from a liquid to a gas or vapor at 40ºF and then the

refrigerant vapor increased in temperature to 50ºF, it has been

superheated by 10ºF.

Fault Codes

Fault Code

Displayed

Condition

Check

FA

Control checks to ensure compressor discharge temperature is rising

when the compressor starts running. T4 sensor (compressor outlet

temperature) must rise at least 20F during the first 30 minutes of run

time.

Check T4 sensor mounting, wiring and resistance.

Check Electronic Expansion Valve (EEV) operation.

Check sealed system for refrigerant leak.

Fb

Control checks to ensure compressor discharge temperature is stable

while the compressor is running. Continuously verifies that T4 sensor

(compressor outlet temperature) is greater than 120F after 30 minutes

of run time.

Check T4 sensor mounting, wiring and resistance.

In cold climates, insulate T4 sensor with mastic.

Check Electronic Expansion Valve (EEV) operation.

Check sealed system for refrigerant leak.

In cold climates, recommend Hybrid or High Demand mode.

FC

Control checks to ensure evaporator is free of frost. Continuously veri-

fies that T3a sensor (evaporator inlet temperature) is greater than 20F

after 30 minutes of run time.

Check T3a sensor mounting, wiring and resistance.

Check Electronic Expansion Valve (EEV) operation.

Check sealed system for refrigerant leak.

Fd

Control checks to ensure evaporator superheat* is OK (controlled by

EEV). Continuously verifies the temperature difference between T3a

sensor (evap inlet temp) and T3b sensor (evap outlet temp) is greater

than 5F after 30 mins of run time. Control also verifies that T3a is

greater than 10F less than T5 ambient sensor.

Check that filter is clean.

Check T3a, T3b and T5 sensor mounting, wiring and resist-

ance.

Check Electronic Expansion Valve (EEV) operation.

Check sealed system for refrigerant leak.

FE

Control checks to ensure the compressor discharge temperature never

exceeds 240F. Continuously verifies that T4 sensor (compressor outlet

temperature) is less than 240F every minute of run time.

Check T4 sensor mounting, wiring and resistance.

Check Electronic Expansion Valve (EEV) operation.

Check sealed system for refrigerant leak.

FF

Control checks to ensure the EEV is operating properly and valve rota-

tion is within range.

Check Electronic Expansion Valve (EEV) operation.

Check T3a and T3b sensors mounting, wiring and resistance.

Check sealed system for refrigerant leak.

FG*

Control checks to ensure Ambient temperature is within an acceptable

range before starting heat pump. Heat pump

operating range is 45ºF < [T5 ambient] <120ºF. If ambient temperature

(as viewed by T5 sensor) is outside of this

range, the unit will switch to Electric/Standard Mode for that heat-

ing cycle only. NO fault code is shown on the display. Note that the

compressor and fan may run for 3 minutes to assess true ambient

temperature.

No failure is assumed, but this information is provided for

completeness.

FH*

Control checks to ensure the compressor load does not exceed a

threshold sufficient to trip the compressor current/temperature over-

load device. It is preferred that the software move the unit into Electric/

Standard Mode rather than tripping the compressor overload device

repeatedly. The logic employs a lookup table to accomplish this, but

a basic summary is: If {T5 ambient temperature range is [90ºF-120ºF]

AND Compressor Current > [3.2 to 3.8A] or T5 ambient temperature

range is [45ºF to 90ºF] AND Compressor Current > 5.5A } then the

control switches operating mode to Electric/Standard for the current

heating cycle, and the FH counter is increased by one. The total FH

count can be viewed in the diagnostics mode, BUT the control will NOT

display a fault code.

Since no fault code is displayed for the Run Condition H, the

fault count information is provided solely to help the techni-

cian

ascertain if the control sees these high ambient

temperature/high current conditions on a regular basis or not.

F

I*

Control checks to ensure evaporator superheat is <20ºF AND the EEV

position is <450 after 30 minutes of run time. If outside these limits,

this provides an early indication of a refrigerant leak. (Note: Target

superheat is generally 10ºF, and EEV generally operates at a position

much lower than 450.)

Check sealed system for refrigerant leak.

Check T3a, T3b, T5 sensor mounting, wiring and resistance.

Check Electronic Expansion Valve (EEV) operation.

F2

T2 tank temperature sensor failure Just before compressor starts,

control checks T2 sensor is within 30F - 170F temperature range.

Check T2 sensor mounting, wiring and resistance.

Use service mode to monitor T2 sensor temperature.

Control assembly may have failed.

F3

Compressor failure

Control energizes compressor, but current sensor detects no current

flow.

Check compressor start capacitor.

Check compressor, overloads, relay and wiring.

Use service mode to manually cycle compressor on/off.

F4

Fan failure

Check fan and wiring.

F5

T3a sensor (evap inlet temperature) failure. The control detects the

thermistor output is at or nearly shorted or open circuit.

Check T3a sensor mounting, wiring and resistance.

Use service mode to monitor T3a sensor temperature.

Control assembly may have failed.

F6

T3b sensor (evap outlet temperature) failure. The control detects the

thermistor output is at or nearly shorted or open circuit.

Check T3b sensor mounting, wiring and resistance.

Use service mode to monitor T3b sensor temperature.

Control assembly may have failed.

F7

T4 sensor (compressor outlet) failure. The control detects the thermis-

tor output is at or nearly shorted or open circuit.

Check T4 sensor mounting, wiring and resistance.

Use service mode to monitor T4 sensor temperature.

Control assembly may have failed.

F8

T5 sensor (ambient temperature) failure. The control detects the ther-

mistor output is at or nearly shorted or open circuit.

Check T5 sensor mounting, wiring and resistance.

Use service mode to monitor T5 sensor temperature.

Control assembly may have failed.

F9

Lower heating element failure. Control energizes lower element, but

current sensor detects no current flow.

Check lower heating element and wiring.

Use service mode to cycle element and check current draw.

Control assembly may have failed.

F10

Upper heating element failure. Control energizes Upper element, but

current sensor detects no current flow.

Check Upper heating element and wiring.

Use service mode to cycle element and check current draw.

Control assembly may have failed.

F11

Dry Tank fault. This test is run within the first 7 minutes after the unit

has powered on. The compressor is engaged for 5 minutes (after a 2

minute wait for the system to ensure the pressures are stabilized) and

the tank temperature, T2, is read and verified it has not risen over 3.5

deg F. If it has, this indicates there is not enough water in the tank for

safe operation.

Check to ensure the tank is full of water.

Check T2 sensor mounting, wiring and resistance.

Use service mode to monitor T2 sensor temperature.

Control assembly may have failed.

bAd linE

(F12)

The voltage is too low at power-up. The control monitors the input line

voltage 5 seconds after power-up, and if the voltage is below 155V, the

fault code will be displayed.

Check electrical supply line connections. Voltage should

measure either 208 VAC or 240 VAC, depending upon power

supply. Badline counts stored in “F12” and can be monitored

via the Control when placed in diagnostics mode.

F13

Stuck Key fault. This indicates there is a button on the front panel that

is stuck down. This button is inoperable. Other buttons work normally.

If the button becomes free, the fault code will clear by itself.

Check to see if all buttons are operable.

Control assembly has failed

DirtyFilter

(F14)

Filter LED is on, and audible alarm is sounding. Filter is too dirty to

enable proper function of unit. Number of “Dirty Filter” counts are

stored in the “F14” code and can be monitored via the Control when it is

placed in Diagnostics Mode.

Check to ensure Filter is clean. Filter cleaning instructions are

found in the owner’s manual.

F15

DataFlash fault. The microcontroller has detected a problem in the

DataFlash (permanent memory storage).

Control assembly may have failed.

*on some models

EEV

CONDENSER COIL

(Non-replaceable)

CAPACITOR VERSION

FAN SHROUD

EVAPORATOR COIL

CAPACITOR VERSION

10

11

13

BLACK
BLACK

YELLOW

BLUE

BROWN

START

CAPACITOR

FAN

TCO

6 Ω

10 Ω

6 Ω

20 Ω

10

YELLOW

BLUE

BROWN

MAIN

BOARD

MAIN

BOARD

FAN

TCO

T5

T2

T3

A

B3

T
T4

V

E

E

COMP

LE

UE

DLB

COMPRESSOR

TCO

170°F

UPPER ELEMENT

T3a

T3b

T4

T2

NO

NO

NO

NO

COM

COM

COM

COM

NC

NC

L1

L2

E

G

N

A

R

O

YELLOW

K

NI

P

VIOLET

T5

(ambient)

BLACK

RED

LOWER ELEMENT

4500W 12.8 Ω ~ 18.75 A

4500W 12.8 Ω ~ 18.75 A

N

W

O

R

B

N

W

O

R

B

W

O

R

B

N

YELLOW

OPTION 1

YELLOW

OPTION 2

BLUE

GRAY

CT101

FA

N

R

OT

A

R

O

P

A

V

E

K202

K204

K203

K201

1

2

3

4

WIRING DIAGRAM

Comp_N

o

Y

A

R

G

BLUE

238-50804-00A 31-75034 03-14

Advertising