Install the upper roof exhaust vent, Vertical enclosures – Thetford 1210 Series GE - Current Manuel d'utilisation

Page 8

Advertising
background image

Installation Manual 8

1. Install the upper roof exhaust vent.

CAUTION:

Make sure that no sawdust, insulation, or other construction debris is

on the refrigerator or in the enclosure. Debris can cause a combustion hazard and

prevent the refrigerator from operating correctly.

NOTE: Tighten the screws of the upper roof exhaust cap to 10 inch-pounds max. Also make

sure that the air flow around the upper roof exhaust cap is not blocked or decreased

by other roof mounted features such as a luggage carrier, an air conditioner, a solar

panel, etc.

2. Align the upper roof exhaust vent above the lower intake exhaust vent (See Art01597):

3. Determine the type of enclosure in a vehicle using an upper roof exhaust vent (See

Art01756):

- If the distance from the face of the enclosure to the inboard edge of the roof exhaust

vent opening [169] is more than 17 1/2 inches, install the roof exhaust vent [12] directly

above the condenser [11] of the refrigerator as a vertical enclosure.

- If the distance from the face of the enclosure to the inboard edge of the roof exhaust vent opening [169] is 17 1/2 inches or less,

install the roof exhaust vent [12] inboard from the condenser [11] of the refrigerator as an offset vertical enclosure.

Install an Upper Roof Exhaust Vent

Install the Baffles for an Upper Roof Exhaust Vent

CAUTION:

Make sure that all horizontal baffles are the full width of the inside of the

enclosure and are in the correct location. If the baffles are not the full width of the enclosure

or incorrectly located, poor cooling performance can result.

Vertical enclosures:

If the enclosure depth is 24 inches or more and less than 25 inches (See Art01780):

- Install a top baffle [13].

- Make sure there is less than 1/4 inch clearance between the baffle and the top of the

refrigerator.

!

!

Art01756

11

12

169

Art01780

13

15