INSTRUCTION LEAFLET - AN43

EN

320023 ind a 07/201

1

Baumer Bourdon-Haenni S.A.S. · 125, rue de la Marre · B.P. 70214 · 41103 Vendôme Cedex · France

Tél. +33 (0)2 54 73 74 75 · Fax France +33 (0)2 54 73 74 74 · Fax Export +33 (0)2 54 73 74 73

[email protected] · www.baumer.com/process

While programming [MENU] LED is light. If programming is proceeding

through USB terminal [RS/USB] LED blinks.

If the device is locked [ ] LED is light.

To go into programming phase press the [MENU] key

Moving forward or back: press [ ]or [ ] keys, press [ ] key to valid the

choice.

Universal input (mA, V, potentiometer)

RTD or thermocouple temperature

20000 count display

keyboard configuration or by USB terminal

2 alarm switches – form C relay

4-20mA or 0-10V analog isolated output

Wide universal power supply

The AN43 is a universal programmable panel meter with capability of transmitter supply, 2 alarm switches and a 4-20mA or 0-10V analog isolated

output. The device configuration is done easily either by the front panel keyboard or by a USB terminal. This configuration can be locked. Filter

function can be selected to smooth a signal, modulo function can in some cases give a comfortable display using always the best specifications

of the instrument.

The AN43 features 2 alarm switches programmable on value, delay, hysteresis, switching status and separation for LED status.

The AN43 is a panel mounting meter, 20000 count 14mm LED with wiring on removable screw-on terminal blocks.

Input and conditionning

Current or voltage or potentiometer input

Input and display programmable by front panel keyboard or by USB terminal

Transmitter supply : 20V – permanent short-circuit max 23mA

Current input shunt value : ≈ 75 Ω

Voltage input impedance 100 MΩ

Accuracy ± 0.1% FS ± 1 count

Thermal drift: max. 100ppm/°C

Range

100mV

1V

10V

Measurement scale

-25mV to 190mV

-0.5V to 1.9V

-0.5V to 11.5V

Temperature input

Range

PT100

TCJ

TCK

TCT

TCE

TCR

TCS

TCB

TCN

TCW5

Scale °C

-200 to

+850

-210 to

1200

-270 to

1372

-270 to

400

-270 to

1000

-50 to

1768

-50 to

1768

0 to

1820

-270 to

1300

0 to

2320

Resolution

0.1°/1°C

0.1°/1°C

0.1°/1°C

0.1°/1°C

0.1°/1°C

0.1°/1°C

0.1°/1°C

0.1°/1°C

0.1°/1°C

0.1°/1°C

Accuracy ±1 pt

0.2°C

1°C

1°C

1°C

1°C

1°C

1°C

1°C

1°C

1°C

Thermal drift

100ppm/°C

50ppm/°C + 0.01°C/°C with cold junction compensation (ADAPTC-VUP terminal)

If not any cold junction compensation is required (external compensation) wire directly thermocouple input.

Otherwise a specific terminal with ambient temperature measurement (ADAPTC-VUP) is mandatory.

Display

-19999 ... +19999 counts red LED - programmable decimal point

Overflow: display dEP. or dEP

Reading rate 10 measurements/second

Power supply

Wide universal 24 to 250Vac and 22 to 140Vdc -Consumption 3.5VA

Environmental

Operating temperature : from 0 ... 50°C

Storage temperature : from -40 ... +85°C

Mechanicals

Noryl UL94V0 case (panel mounting) – front panel waterproof IP54

Wiring on removable screw-on terminal blocks

Dimensions : front panel 48x96

Overall depth 104mm panel width max 10mm

Cut out 45(-0/+0.5) x 91.5(-0/+0.5)mm- Fixed by means of screw clips

4-20mA or 0-10V Analog isolated output

SA2 (0-10V) - SA3 (4-20mA) - SA4 (4-20mA passive)

Isolation voltage input/output : 500 V eff

Output load 400 Ω (8V) max current 22mA

Accuracy : full scale 0.15% - zero 0.1%

Repeatability : 0.1% - Thermal drift 100ppm/°C

Default value > 21mA or 10,5V

Alarms

2 independent alarm switches programmable on value, delay, hysteresis, relay status and separation for LED status.

LED alarm status on front panel.

2 relays form C - 1A 220V cosϕ 0.7

Wiring

Input terminal wiring Cn2

Analog isolated output terminal wiring Cn4

Alarm wiring

Alarm switches are available on terminal Cn3

Power supply wiring

Primary supply is connected on terminal Cn1

The equipment bears the CE mark, in accordance with directives

89-336/CEE. This system meets the following standards: EN50081-2

and

EN 50082-2. Complementary tests have been carried out as per other

standards. Please call our technical team for more information.

Display configuration and programming

1. Input configuration

Go into programming phase and using moving keys reach « cFG » function, valid.

Possible choices : « cour » (current) « tEnS » (voltage) « Pt » « Tc » « Pot » choice the desired input and valid

Reach « Ent »function, valid.

Depending on previous choice possible ranges are visible using the moving keys.

Possible choices :

Current : « 4-20 » - « 0-20 »

Voltage : « 0-10 » - « 0-1.0 » - « 0-0.1 »

Pt100 : « 2FiL » (2-wire) - « 3FiL » (« 6wire) - « diFF » (difference)

Thermocouple : J, K, T, E, R, S, B, N, W5

Valid the choice

2. Display configuration

While in programming phase reach « PEAF » function and valid.

The value desired for the full scale of display is displayed. Use the moving keys to increase or decrease the value. Valid.

Reach « 0-AF » function.

The bottom scale value is displayed.

Use the moving keys to increase or decrease the value. Valid.

3. Decimal point configuration

In programming phase reach « PdEc » function

Use the moving keys to change the decimal point position. When it is correct, valid.

4. Analog output configuration

Reach « PESA» function, use the moving keys to adjust the output full scale. Valid.

Reach « 0-SA » function, adjust the output bottom value using moving keys.

Reach « dEc » function, choice « oui » if a zero offset is needed (4-20mA output case). Valid

« t SA » function drives an output variation independently from measurement for testing.

5. Alarm 1 configuration

Reach « ALr1 » function

Use moving keys to increase or decrease the value.

Valid. Same way for all the alarm functions.

« HYS1 » - hysteresis value in display counts

« dEL1 » - delay value in seconds max 25.5s

« rEL1 » - relay status NO or NF (NC)

« LEd1 » - separation LED led status versus relay refer chart below

6. Measurement filter programming

The filter allows smoothing the measurement value.

It is programmable from 0 to 60 seconds

In programming phase reach « FiLt » function.

Use the moving keys to increase or decrease the value. Valid

7. Display modulo programming

Display modulo is programmable on 1, 2, 5 or 10 (0)

In programming phase reach « Mod » function.

Use the moving keys to select the desired choice. Valid

8. Linearization validation

Choices « yes » or « no » using moving keys.

Linearization is programmable through USB terminal. Valid.

9. Lock and unlock keyboard

Menu lock : Get on the device pressing [1] key – alarms are still programmable

Complete lock : get on the device pressing [2] key

Unlock : get on the device pressing [1] and [2] keys

Keyboard can be locked using USB programming.

10. Alarm values display

Pressing [1] or [2] keys, the device displays the considered alarm value.

When alarm value is crossed LED inside the adequate key light on or off according programming.

11. Peak value display

Press [ ] : Maximum peak value display

Press [ ] : Minimum peak value display

Press [ ] and [ ] : reset the peak values in memory

12. Overflow

Measurement overflow : display « dEP »

Display capacitance overflow > 19 999 counts : the 4 up segments of each digit are lighted

Display capacitance overflow < -19 999 counts : the 4 down segments of each digit are lighted

Analog output takes an upper default value 21mA or 10,5V.

Supplying a

4-20mA

transmitter

4-20mA or

0-20mA

loop receiver

Voltage 100mV,

1V or 10V

Potentiometer

PT100

3-wire

PT100

2-wire

Difference

between 2

PT100

Thermocouple

with external

compensation

Thermocouple

with

compensated

terminal

ADAPTC-VUP

External cold junction

Make a short circuit

Output

Output

Output

active

passive

Alarm – LED and relay status

Relay/LED

Measurement < alarm

Measurement > alarm