Lenze E82MV752 4Bxxx Manuel d'utilisation
Page 13

13
EDK82MV752-BB DE/EN/FR 1.0
Fuses and cable cross-sections according to UL
Supply conditions
Range
Description
Fuses
z
Only in accordance with UL 248
z
System short-circuit current up to 5000 A
rms
: All classes are permissible
z
System short-circuit current up to 50000 A
rms
: Only classes ”CC”, ”J”, ”T” or ”R”
permissible
Cables
z
Only in accordance with UL
z
The cable cross-sections specified in the following apply under the following
conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!
8200 motec
Rated fuse current / cable cross-section
Fuse
Circuit-breaker
max. current
L1, L2, L3, N, PE
max. current
Type
L1, L2, L3, N, PE
Type
[A]
[AWG]
[A]
[AWG]
Mains 1/N/PE AC 230/240 V
E82MV251_2B
10
16
15
cdefgh
14
E82MV371_2B
10
16
15
14
Mains 3/PE AC 400/500 V
E82MV551_4B
6
18
15
degh
14
E82MV751_4B
6
18
15
14
E82MV152_4B
10
16
15
14
E82MV222_4B
20
12
20
12
E82MV302_4B
20
12
20
degh
12
E82MV402_4B
20
12
20
12
E82MV552_4B
25
10
25
10
E82MV752_4B
35
8
35
d
8
c
Siemens 5SJ4...-7HG41, Characteristic C
d
Siemens 5SJ4...-7HG42, Characteristic C
e
Moeller FAZ-C, Characteristic C
f
ABB S200U, Characteristic K
g
ABB S200UP, Characteristic K
h
Schneider Electric Multi9 C60, Characteristic C