2 typical chimney installation – Napoleon Fireplaces High Country 3000 - NZ3000 Manuel d'utilisation

Page 15

Advertising
background image

W415-0711 / D / 05.09.13

15

EN

* The fi rst fl ue offset closest to the top of the appliance must be a minimum distance of 12” (304.8mm)
from the top of the appliance.

1.

Move the appliance into position. Try to center the exhaust fl ue of the appliance,
midpoint between two joists to prevent having to cut them. Use a plumb bob to
line up the centre.

2.

Cut and frame an opening in the ceiling to provide a
minimum clearance of 2” (50.8mm) between the
outside of the chimney and any combustible material.
DO NOT FILL THIS SPACE WITH ANY TYPE OF
MATERIAL!
Nail headers between the joists for extra
support. Firestop spacers must be placed on each
framed opening in any fl oor or ceiling that the chim-
ney passes through.

3.

Hold a plumb bob from the underside of the roof
to determine where the opening in the roof should
be. Cut and frame the roof opening maintaining
proper 2” (50.8mm) clearances.

NOTE: 30° or 45° offsets may be installed back to
back.

63.5A

15 FT

(4.6m)

MINIMUM

34 FT

(10.4m)

MAXIMUM

RAIN CAP

RAIN CAP

RAIN CAP

STORM COLLAR
ROOF FLASHING

STORM COLLAR
ROOF FLASHING

STORM COLLAR
ROOF FLASHING

ATTIC INSULATION

SHIELD

ATTIC INSULATION

SHIELD

ATTIC INSULATION

SHIELD

CEILING RADIATION

SHIELD

OFFSET

SUPPORT

OFFSET

SUPPORT

FIRESTOP

FIRESTOP

12” (304.8mm)

MIN*

15 FT

(4.6m)

MINIMUM

34 FT

(10.4m)

MAXIMUM

12” (304.8mm)

MIN*

15 FT

(4.6m)

MINIMUM

34 FT

(10.4m)

MAXIMUM

2"

(50.8mm)

Min.

Typical Roof Joist Framing

Typical Joist Framing

2"

(50.8mm)

Min.

2" (50.8mm)

Min.

2"

(50.8mm)

Min.

STRAIGHT CHIMNEY

SINGLE OFFSET

CHIMNEY

DOUBLE OFFSET

CHIMNEY

HEADERS

FIRESTOP SPACER -
UNDERSIDE OF JOIST

4.2 TYPICAL CHIMNEY INSTALLATION